USER SETTINGS LOG
TEEJET TECHNOLOGIES
98-01557-EN-R1_A4LT-DynaJetIC7140-UserSettings.docx
3
Main Setup -> OEM Settings
Description
Factory Default
Range/Options
Suggested Setting
Use Default
PWM Frequency
20 Hz
5 - 25 Hz
☐
On Pulse Duration
38 counts
0 - 128
☐
Hold Current Frequency Adjustment
10 counts
5 - 20
☐
Hold Current Duty Cycle
5 counts
0 - 20
☐
Phase Offset
128 counts
0 - 255
☐
Jump Point
0.35 bar / 5 psi
0.00 - 2.11 bar / 0 - 31 psi
☐
Maximum Duty Cycle
92%
70% - 100%
☐
PWM Off Time
20
0 - 100
☐
Low Voltage Limit
11.0V
0.0 - 20.0V
☐
High Voltage Limit
15.0V
0.0 - 20.0V
☐
Low Amps Limit
0.4A
0.0 - 20.0A
☐
High Amps Limit
1.2A
0.0 - 20.0A
☐
High Pressure Alarm
6.0 bar / 87 psi
4.0 - 25.0 bar / 58 – 363 psi
☐
Droplet Size Damping
0.10
0.01 - 0.99
☐
ECU Orientation
Horizontal, Label Up
•
Horizontal, Label Up
•
Horizontal, Label Down
•
Vertical, Connectors Up
•
Vertical, Connectors
Down
•
Vertical, Left Edge Up
•
Vertical, Right Edge Up
☐
Regulation Base
Pressure Based
•
Pressure Based
•
Flow Based
☐
Solenoid Error State
All Open
•
All Open
•
All Closed
☐
Solenoid Disengage State
All Open
•
All Open
•
All Closed
☐
English-International
www.teejet.com
© TeeJet Technologies 2020