3-49
3.8 EMC Filter Disconnection
EMC filter may be disconnected:
Inverter drives with built-in EMC filter are not suitable for connection to certain type of supply
systems, such as listed below; in these cases the RFI filter can be disabled.
In all such cases consult your local electrical standards requirements.
IT type supply systems (ungrounded) & certain supply systems for medical equipment.
For ungrounded supply systems If the filter is not disconnected the supply system becomes
connected to Earth through the Y capacitors on the filter circuit. This could result in danger and
damage to the Drive.
Remove steps :
1 using a screwdriver to remove the front cover.
2 use screwdriver to loosen the screw.
3 using a screwdriver to remove short film.
4 use screwdriver to tighten the screws.
Note:- Disconnecting the EMC filter link will disable the filter function, please consult your local
EMC standards requirement.
(1) (2) (3) (4)