App3-1
Appendix 3: E510 MODBUS Communication protocol
1. Communication Data Frame
E510series inverter can
be controlled by a
PC or other controller with the Communication
protocol, Modbus ASCII Mode & Mode RTU, RS485 or RS232. Frame length maximum 80
bytes.
1.1 Hardware installation
Slave E510
Station 01
Slave E510
Station 02
Slave E510
Station 03
Slave E510
Station FE
controller
(PLC / HMI or
PC )
Option Card
Option Card
Option Card
Option Card
RS-485
Interface
A B
A B A B
A B
Response
Request
** The network is terminated at each end with an external terminating resistor (120
Ω
,
1/4w)**
1.2 Data format ASCII MODE
STX(3AH)
Start bit = 3AH
Address Hi
Address Lo
Communication Address(Station):
2-digit ASCII Code
Function Hi
Function Lo
Function Code (command):
2-digit ASCII Code
Command Start Address
Command Start Address
Command Start Address
Command Start Address
command Start byte:
4-digit ASCII Code
Data length
Data length
Data length
Data length
The length of the command:
4-digit ASCII Code
LRC Check Hi
LRC Check Lo
LRC Check Code:
2-digit ASCII Code
END Hi
END Lo
End Byte :
END Hi = CR(0DH) , END Lo= LF(0AH)
120
Ω
1/4w
120
Ω
1/4w
Summary of Contents for e510 series
Page 1: ......
Page 8: ...2 1 Chapter 2 Part Number Definition 2 1 Model Part Number...
Page 13: ...3 4 Screw M4 Screw M4...
Page 34: ...3 25 c Three phase 200V 8 10HP 400V 8 15HP E510 Frame 3 E510 Frame 3 NEMA1...
Page 35: ...3 26 d Three phase 200V 15 20HP 400V 20 25HP E510 Frame 4 E510 Frame 4 NEMA1...
Page 43: ...3 34 3 5 2 Single Three phase Model 200V E510 2P5 H E510 201 H E510 202 H E510 203 H...
Page 197: ......