3-18
3.3 Wiring Guidelines
3.3.1 Power Cables
Supply power cable must be connected to TM1 terminal block, terminals
L1(L), L2, L3(N).
L1(L) and L3(N) for single phase 230V supply.
Motor cable must be connected to TM1 terminals. T1, T2, T3.
Warning:-
Connection of supply line cable to terminals T1,T2, T3 will result in serious
damage to the drive components.
Example power connections: Inverter with dedicated power line.
Inverter
IM
Power
MCCB
¾
Install a Supply RFI filter or Isolation transformer when the power source is shared with other
high power electrical equipment as shown below.
Inverter
IM
Machine
Insulation transformer
Power
MCCB
3.3.2 Control Cable selection and Wiring
Control cables should be connected to terminal block TM2.
Choose power & Control cables according to the following criteria:
-
¾
Use copper wires with correct diameter and temperature rating of 65/70
°C.
¾
Minimum cable voltage rating for 200V type inverters should be 300VAC. Minimum cable
voltage rating for 400V type inverters should be 600VAC.
¾
Route all cables away from other high voltage or high current power lines to reduce
interference effects.
¾
Use a twisted pair shielded cable and connect the shield (screen) wire to the ground terminal at
the inverter end only. Cable length should not exceed 50 meters.
Inverter
IM
Machine
RFI
Filter
Power
MCCB
Shielding sheath
Protective covering
Connect the shield to
Inverter ground terminal
Do not connect this end
Summary of Contents for e510 series
Page 1: ......
Page 8: ...2 1 Chapter 2 Part Number Definition 2 1 Model Part Number...
Page 13: ...3 4 Screw M4 Screw M4...
Page 34: ...3 25 c Three phase 200V 8 10HP 400V 8 15HP E510 Frame 3 E510 Frame 3 NEMA1...
Page 35: ...3 26 d Three phase 200V 15 20HP 400V 20 25HP E510 Frame 4 E510 Frame 4 NEMA1...
Page 43: ...3 34 3 5 2 Single Three phase Model 200V E510 2P5 H E510 201 H E510 202 H E510 203 H...
Page 197: ......