4-58
07- Start/Stop Command Setup
07- 00
Momentary power loss and restart
Range
【
0
】
:Momentary Power Loss and Restart Disable
【
1
】
:Momentary Power Loss and Restart Enable
¾
If the input power supply due to sudden increase in supply demand by other equipment results in
voltage drops below the under voltage level, the inverter will stop its output at once.
¾
When
07-00
=
【
0
】
.
On power loss, the inverter will not start.
¾
When 07-00 =
【
1
】
.Aafter a momentary power loss, inverter will restart
with half frequency before
power loss
, and there is no limitation on number of restarts.
¾
On power loss, as long as the inverter CPU power is not completely lost, the momentary
power loss restart will be effective, restart will be according to setting of parameters 00-02 &
07-04 and status of External run switch.
Caution:-
After any power loss if the Run mode is set to External by parameter 00-02=1 and if Direct
start on power up is also selected by parameter 07-04=0, please note that the inverter will run on
resumption of power.
To ensure safety of operators and to avoid any damages to the machinery, all necessary safety
measure must be considered, including disconnection of power to the inverter.
07- 01
Auto Restart Delay Time
Range
【
0.0~800.0
】
s
07- 02
Number of Auto Restart Attempts
Range
【
0~10
】
¾
07-
02=
【
0
】
: The inverter will not auto restart after trips due to fault.
¾
07-
02>
【
0
】
,
07- 01=
【
0
】
.After a trip due to fault the inverter will run
with half frequency before
power loss,
and restarts after an internal delay of 0.5 seconds.
¾
07- 02>
【
0
】
,
07- 01>
【
0
】
,
After a fault trip the inverter will run with half frequency before power
loss, and restart with a delay according the preset in parameter 07-01.
¾
Note:- Auto restart after a fault will not function while DC injection braking or
decelerating to stop
07- 03
Reset Mode Setting
Range
【
0
】
:Enable Reset Only when Run Command is Off
【
1
】
:Enable Reset when Run Command is On or Off
¾
07-03=0 Once the inverter is detected a fault, please turn Run switch Off and then On again to
perform reset, otherwise restarting will not be possible.
07- 04
Direct Running on Power Up
Range
【
0
】
:Enable Direct Running on Power Up
【
1
】
:Disable Direct Running on Power Up
07- 05
Delay-ON Timer (Seconds)
Range
【
1.0~300.0
】
Sec
¾
When direct run on power up is selected by 07-04=0 and the inverter is set to external run by
(00-02/00-03=1), if the run switch is ON as power is applied, the inverter will auto start.
It is recommend that the power is turned off and the run switch is also off to avoid possibility of
injury to operators and damage to machines as the power is reapplied.
Note: IF this mode is required all safety measures must be considered including warning
labels
.
¾
When direct run on power up is disabled by 07-04=1 and if the inverter is set to external run by
(00-02/00-03=1), if the run switch is ON as power is applied, the inverter will not auto start and
the display will flash with STP1. It will be necessary to turn OFF the run switch and then turn ON
again to start normally.
Summary of Contents for e510 series
Page 1: ......
Page 8: ...2 1 Chapter 2 Part Number Definition 2 1 Model Part Number...
Page 13: ...3 4 Screw M4 Screw M4...
Page 34: ...3 25 c Three phase 200V 8 10HP 400V 8 15HP E510 Frame 3 E510 Frame 3 NEMA1...
Page 35: ...3 26 d Three phase 200V 15 20HP 400V 20 25HP E510 Frame 4 E510 Frame 4 NEMA1...
Page 43: ...3 34 3 5 2 Single Three phase Model 200V E510 2P5 H E510 201 H E510 202 H E510 203 H...
Page 197: ......