App3-5
4
Inverter Control
4.1 Command Data (Readable and Writable)
Register No.
Bit
Content
2500H
Reserved
Operation Signal
0
Operation Command 1 : Run 0 : Stop
1
Reverse Command 1 :Reverse 0 :Forward
2
Abnormal 1 : EFO
3
Fault Reset 1 : Reset
4
Jog Forward Command 1 : Jog Forward
5
Jog Reverse Command 1 : Jog Reverse
6
Multi-function CommandS1 1 :“ON” 0:“OFF”
7
Multi-function CommandS2 1 :“ON” 0:“OFF”
8
Multi-function CommandS3 1 :“ON” 0:“OFF”
9
Multi-function CommandS4 1 :“ON” 0:“OFF”
A Multi-function CommandS5 1 :“ON” 0:“OFF”
B
Multi-function CommandS6 1 :“ON” 0:“OFF”
C
Relay R1 1 :“ON” 0:“OFF”
D
Relay R2 1 :“ON” 0:“OFF”
2501H
E~F
Reserved
2502H
Frequency Command
2503~251FH Reserved
Note: Write in zero for Not used BIT, do not write in data for the reserved register.
4.2 Monitor Data (Only for reading)
Register No.
Bit
Content
State Signal
0
Operation state 1 : Run 0 : Stop
1
Direction state 1 : Reverse 0 : Forward
2
Inverter operation prepare state 1:ready 0 : unready
3
Abnormal 1 : Abnormal
4
DATA setting error 1 : Error
2520H
5-F Reserved