4-44
03-17
Brake Release Level
Range
【
0.00~20.00
】
Hz
03-18
Brake Engage Level
Range
【
0.00~20.00
】
Hz
¾
If 03-11 =
【
14
】
¾
In accelerating mode. RY will be ON as soon as the actual output frequency reaches the external
Brake release level set in parameter 03-17.
¾
In decelerating mode, RY will be OFF as soon as the actual output frequency reaches the external
Brake engage level set in parameter 03-18.
Timing diagram for 03-17 < 03-18 is shown below:
03-17
03-18
03-11=14
RUN
command
Hz
T
ON
OFF
RUN
STOP
Timing diagram for 03-17 > 03-18 is shown below:
03-18
03-17
RUN
command
03-11=13
Hz
T
ON
OFF
RUN
STOP
03- 19
Relay Output Status Type
Range
【
0
】
:A (Normally open)
【
1
】
:B (Normally close)
¾
When
03-19=0,
¾
When the set conditions of 03-11,03-12 are met , relay contact is closed, otherwise it will be open..
¾
When
03-19=1,
¾
When the set conditions of 03-11,03-12 are met ,relay contact will open,Otherwise it will be closed..
03- 20
Internal / External Multi-Function Input Terminal Selection
Range
【
0~63
】
¾
The parameter of 03-02 is to determine the multi-function input terminals need for internal or external
multi-function input terminals. If you select the internal multi-function input terminal, the terminal's
open, closed decision by the parameter 03-21 decision.
03-20 representatives from each of the following:
03- 20= 0 0 0 0 0 0
S6 S5 S4 S3 S2 S1
Summary of Contents for e510 series
Page 1: ......
Page 8: ...2 1 Chapter 2 Part Number Definition 2 1 Model Part Number...
Page 13: ...3 4 Screw M4 Screw M4...
Page 34: ...3 25 c Three phase 200V 8 10HP 400V 8 15HP E510 Frame 3 E510 Frame 3 NEMA1...
Page 35: ...3 26 d Three phase 200V 15 20HP 400V 20 25HP E510 Frame 4 E510 Frame 4 NEMA1...
Page 43: ...3 34 3 5 2 Single Three phase Model 200V E510 2P5 H E510 201 H E510 202 H E510 203 H...
Page 197: ......