4-125
03-1X=0:
During Running
ON: Run command is ON or output frequency is greater than 0
OFF: Run command is OFF and the inverter is stopped.
03-1X=1:
Fault contact output
Output is active during fault condition.
Note:
Communication error (CF00, CF01) do not activate the fault contact.
03-1X=2:
Frequency Agree
Output is active when the output frequency falls within the frequency reference minus the frequency detection
width (o3-14).
03-1X=3:
Setting Frequency Agree
Output is active when the output frequency falls within the frequency detection width (03-14) of the set frequency
detection level (o3-13).
03-1X=4:
Frequency detection 1
Output is active when the output frequency rises above the frequency detection level (03-13) + frequency
detection width (o3-14) and deactivates when the output frequency falls below frequency detection level (o3-13).
03-1X=5:
Frequency detection 2
Output is active when the output frequency is below the frequency detection level (03-13) + frequency detection
width (03-14) and turns off when the output frequency falls below frequency detection level.
Refer to table 4.3.9 for the operation of frequency detection.
03-1X=6:
Automatic restart.
Output is active during an auto-restart operation.
03-1X=7:
Baseblock (B.B.)
Output is active during a momentary AC power loss
03-1X=8:
Rapid Stop
Output is active during a rapid stop
03-1X=9:
Baseblock (B.B.)
Output is active when the inverter output is turned off during a Baseblock command.
03-1X=10:
Motor Overload Protection (OL1)
Output is active during motor overload detection (OL1)
03-1X=11:
Drive Overload Protection (OL2)
Output is active during inverter overload detection (OL2)
03-1X=12:
Over torque detected (Normally Open)
Output is active during an over torque detection see parameters 08-13 ~ 08-16.
03-1X=13:
Preset Output Current Reached
When output current > 03-15 and output current > 03-15 duration >03-16, it is ON.
03-1X=14:
Motor Overload Protection (OL1)
Output is active when brake control is active
03-1X=15:
Motor Overload Protection (OL1)
Output is active when PID feedback signal is lost (e.g. wire break)