4-196
11-66
2/3 Phase PWM Switch Frequency
Range
【
6.00~60.00
】
Inverter will modulation mode from 2 phase PWM to 3 phase PWM when the output frequency is higher than the
value set in parameter 11-66.
11-67
RPWM Frequency Bias
Range
【
0~12000
】
11-68
RPWM Switch Frequency
Range
【
6.00~60.00
】
Hz
Noise detection function is enabled when the inverter output frequency rises above the value set in parameter
11-68 and the Inverter will change the electromagnetic noise in operation according to the PWM mode setting of
parameter 11-67.
Notes:
When 11-02=2, the sum of 11-01+11-67 cannot higher than the upper limit of carrier frequency, please refer to
the error conditions:
An error message is shown when parameter 11-02=2 and the sum of 11-66+11-67 is higher than the upper limit
of the carrier frequency, adjust the value of 11-02 or 11-67.
11-69
Gain of Preventing Oscillation 2
Range
【
0.00~200.00
】
%
Increase value in steps of 0.01 in case of motor vibration in ND mode.
11-70
Upper Limit of Preventing Oscillation 2
Range
【
0.01~100
】
%
Set upper limit for the oscillation prevention function.
11-71
Time Parameter of Preventing Oscillation 2
Range
【
0~30000
】
ms
Set oscillation 2 prevention response time. A lower value increases response time but may cause instability.