4-34
Group 08 Protection Parameters
Code
Parameter Name
Setting Range
Default
Unit
Control mode
Attribute
V/F SLV
PM
SLV
Phase Loss Protection
1
:
Enable
08-13
Selection of
Over-Torque Detection
0
:
Over-Torque Detection is Disabled.
0
-
O
O
O
1
:
Start detection when reaching the set
frequency.
2
:
Start detection during running
08-14
Selection of
Over-Torque Action
0
:
Decelerate to Stop when Over Torque is
Detected.
0
-
O
O
O
1
:
Display Warning when Over Torque is
Detected. Continue operation.
2
:
Coast to Stop when Over Torque is
Detected
08-15
Level of Over-Torque
Detection
0~300
160
%
O
O
O
08-16
Time of Over-Torque
Detection
0.0~10.0
0.1
Sec
O
O
O
08-17 Fire Mode
0
:
Disabled
0
-
O
O
O
1
:
Enabled
08-21
Limit of Stall Prevention
During Acceleration
1~100
50
%
O
O
O
08-22
Stall Prevention
Detection Time During
Run
2~100
100
ms
O
O
O
08-23
Ground Fault (GF)
Selection
0
:
Disable
0
-
O
O
O
1
:
Enable
08-30
STO function selection
(***)
0
:
Deceleration to Stop
0
-
O
O
O
1
:
Coast to Stop
08-35
Motor Overheating
Fault Selection
0
:
Disable
0
-
O
O
O
1
:
Deceleration to Stop
2
:
Coast to Stop
3
:
Continue Running
08-36
PTC Input Filter Time
Constant
0.00 ~ 5.00
2.00
Sec
O
O
O
08-38 Delay Time of Fan Off
0~600
60
Sec
O
O
O
08-39
Delay Time of Motor
Overheat Protection
1~300
60
Sec
O
O
O
08-40
Motor2 Acceleration
Stall Prevention Level
20~200
HD: 150
%
O
O
X
ND: 120
08-41
Motor2 Acceleration
Stall Prevention Limit
1~100
50
%
O
O
X
08-42 PTC Protection Level
0.1~10.0V
0.7
V
O
O
O
08-43 PTC Restart Level
0.1~10.0V
0.3
V
O
O
O