4-126
03-1X=18:
PLC status (setting =18)
Output is active when operation command parameter (00-02) is set to 3: PLC Control.
03-1X=19:
PLC control contact
Output is controlled by the PLC logic
03-1X=20:
Zero-speed
Output is active during zero-speed when output frequency
≦
minimum output frequency (01-08).
t
t
ON
OFF
01-08(Fmin)
Output
Frequency
Zero
Speed
Figure 4.3.26 Zero speed operation
03-1X=30:
Motor 2 Selection
Output is active when motor 2 is selected
03-1X=54:
Short Circuit Braking
Output is active during short circuit braking
03-1X=55:
Low Current Detection
Output is active when low current detection is active, output current <= 03-48.
03-13
Frequency detection Level
Range
【
0.0~599.0
】
Hz
03-14
Frequency detection width
Range
【
0.1~25.5
】
Hz
Frequency detection Level: set the multi-function output terminals R1A-R1C, R2A-R2C or PH1 (03-11, 03-12) to
the desired detection level and bandwidth for use with multi-function output functions 1 to 6.
The time charts for the Frequency Agree Detection operation are shown in the following table 4.3.30.