3-32
400V Class
:
Three phase
Model
:
E510-
□□□- H3(F*)-U
430
440
Horse power (HP)
30
40
HD/ND Suitable motor capacity (kW)
22/30
30/37
HD/ND Rated output current (A)
45/58
60/73
HD/ND Rated capacity (KVA)
34.3/44.2
45.7/55.6
Input voltage range(V)
Three phase : 380~480V,50/60HZ
Allowable voltage fluctuation
+10%-15%
Output voltage range(V)
Three phase : 0~480V
Input current (A)*
48.9/63
65.2/78.3
Inverter net weight (KG)
20
30
Allowable momentary power loss time(s)
2.0
Enclosure
IP20/NEMA1
Model
:
E510-
□□□- H3(F*)-U
450
460
475
Horse power (HP)
50
60
75
HD/ND Suitable motor capacity (kW)
37/45
45/55
55/75
HD/ND Rated output current (A)
75/88
91/103
118/145
HD/ND Rated capacity (KVA)
57.2/67.1
69.3/78.5
89.9/111
Input voltage range(V)
Three phase : 380~480V,50/60HZ
Allowable voltage fluctuation
+10%-15%
Output voltage range(V)
Three phase : 0~480V
Input current (A)*
81.5/95.7
98.9/112
130/159
Inverter net weight (KG)
30
30
35
Allowable momentary power loss time(s)
2.0
2.0
2.0
Enclosure
IP20/NEMA1
* F Version models are not available as standard product in Americas.