4-143
Example 1:
Automatic operation mode
– Single cycle
In this example the inverter executes a single cycle and then stops.
Parameter Settings:
06-00 =
1 or 4 (Single cycle operation)
06-32~06-34= 1 (Forward for multi-step speed 0 - 2)
06-47=
2 (Reversal for multi-step speed 15)
06-35~06-46= 0 (Stop for multi-step speed 3 - 14)
05-01=
15 Hz (Multi-step speed 0:15 Hz)
06-01=
30 Hz (Multi-step speed 1:30 Hz)
06-02=
50 Hz (Multi-step speed 2:50 Hz)
06-15=
20 Hz (Multi-step speed 15:20 Hz)
06-16=
20 sec (Operation time stage 0:20 sec)
06-17=
25 sec (Operation time stage 0:25 sec)
06-18=
30 sec (Operation time stage 0:30 sec)
06-31=
40 sec (Operation time stage 15:40 sec)
Freq.
50 Hz
30 Hz
15 Hz
20 Hz
20s
25s
30s
40s
05-01
06-01
06-02
06-15
06-16
06-17
06-18
06-31
Figure 4.3.52 Single cycle operation (Stop)