4-68
01 V/F Control Parameters
01-00
Volts/Hz Patterns
Range
【
0~FF
】
The V/F curve selection is enabled for V/F mode. Make sure to set the inverter input voltage parameter 01-14.
There are three ways to set V/F curve:
(1) 01-00 = 0 to 0E: choose any of the 15 predefined curves (0 to 17).
(2) 01-00 = 0F, use 01-02~01-09 and 01-12 ~ 01-13, with voltage limit
(2) 01-00 = FF, use 01-02~01-09 and 01-12 ~ 01-13, without voltage limit
The default parameters (01-02 ~ 01-09 and 01-12 ~ 01-13) are the same when 01-00 is set to 0F and 01-00 is set
to 1 depending on the initialization mode.
Parameters 01-02 ~ 01-13 are automatically set when any of the predefined V/F curves are selected.
Consider the following items as the conditions for selecting a V/F pattern.
(1) The voltage and frequency characteristic of motor.
(2) The maximum speed of motor.
Note:
Parameter 01-00 V/f Pattern setting is not affected by drive initializing (see parameter 13-08).
01-03 (Vmax)
01-05 (Vmid2)
01-07 (Vmid1)
01-09 (Vmin)
01-08
01-06
01-04
01-02
(V)%
Hz
599.00
Output
Voltage
Output
Frequency
01-02
(the output frequency Versus max. voltage)
The Output Voltage Limit Curve
(the voltage limit for 400V units is
twice the limit of 200V units)
0
5V
40V
250V
01-02
40