4-135
Gain:
Use parameter 04-12 to adjust the gain for AO. Adjust the gain so that the analog output (10V) matches
100% of the selected analog output signal (04-11 for AO).
Bias:
Use parameter 04-13 to adjust the bias for AO. Adjust the bias so that the analog output (0V) matches 0%
of the selected analog output signal (04-11 for AO).
Monitored items
100%
0%
Analog Output Signal
10V(or 20mA) × Gain
(20mA) 10V
(4mA) 0V
{
Bias
Figure 4.3.51 Analog output level adjustment
Analog output terminal function selection (04-11)
Please refer to the following table 4.3.33.
04-11
parameter
setting
Function
(Keypad display)
Monitoring
Parameters
12 Group
Control Mode
VF
SLV
PMSLV
0
Output Freq
12-17
O
O
O
1
Freq Ref
12-16
O
O
O
2
Output Voltage
12-19
O
O
O
3
DC Voltage
12-20
O
O
O
4
Output Current
12-18
O
O
O
Table 4.3.33 Selection of analog output terminals function (04-11)
F-Gain Function:
The F- Gain function offers the ability to use a single frequency reference set by a master potentiometer to more than
one inverter. The master frequency can be scaled by three individual potentiometers for each inverter as show in the
diagram below.
To enable set parameter 04-16=1 and set parameter 00-05 =2 (external Analog input AI1). Analog input 2 (AI2) can
now be used for external scaling (potentiometer).