4-175
10 PID Parameters
10-00
PID target value source setting
Range
【
0
】
: Keypad
【
1
】
: AI1 (Analog Input 1)
【
2
】
: AI2 (analog Input 2)
【
3
】
: Communication
【
4
】
: Use 10-02 setting
Parameter 10-00 sets the PID target selection when frequency source selection is set to PID parameters 00 - 05 /
00 - 06= 6.
10-01
PID feedback value source setting
Range
【
0
】
:
Keypad
【
1
】
: AI1 (Analog Input 1)
【
2
】
: AI2 (analog Input 2)
【
3
】
:
Communication
Parameter 10-01 sets the PID feedback selection when frequency source.
Note:
10-00 and 10-01 cannot be set to the same value or keypad will show an SE05 alarm.
AI2
AI1
Communication
10-26
10-27/10-28
10-00=0
10-00=2
10-00=4
PID target
SFS
ON
PID setting point
Target
Value
10-01=1
10-01=2
10-01=3
PID feedback
PID feedback display
unit conversion
Feedback
Value
10-00=1
10-00=3
Keypad display
AI1
AI2
Communication
10-02 setting
Keypad display
10-01=0
Figure 4.3.80a PID input selection