13
to avoid general differential interventions due to possible interference generated by the EC fans,it is advisable to use
a type B or B+ differential switch with a rated 30 mA intervention differential current for the exclusive use of the unit.
Check that the electrical components chosen for installation (circuit breaker, differential, cable section and terminals)
are suitable for the electrical power of the unit installed and that they take into account the starting currents as well
as the maximum load that can be reached (the data are indicated in the paragraph Technical specifications and on
the unit identification plate)
Always avoid passing the electrical cables in direct contact with pipes or other system components.
Attention! Be sure to have disconnected power from the unit (power cable disconnected) before opening the electrical
boxes or the unit.
INSTALLAZIONE RESISTENZA ANTIGELO
(OPZIONALE)
/ INSTALLATION OF ANTIFREEZE HEATING ELEMENT
(OPTIONAL)
L’unità può essere dotata di un riscaldatore elettrico da canale installabile come protezione antigelo.
Vista la varietà di tipologie esistenti, le istruzioni di installazione dettagliate vengono fornite con il riscaldatore
stesso. Qui sotto sono riportate comunque alcune indicazioni.
Funzione antigelo: in questo caso il riscaldatore, in inverno quando la temperature esterna scende sotto gli
0 C, ha la funzione di riscaldare l’aria in ingresso sull’unità in modo da evitare la formazione di ghiaccio sul
pacco di scambio dell’unità.
Installazione:
• montare il riscaldatore sul condotto di “Rinnovo” (presa aria esterna);
• collegare il riscaldatore alla rete elettrica;
• impostare il termostato di regolazione tra 0 e 3 C (se la resistenza ha 2 stadi impostare un termostato tra -2
e 0 C e l’altro tra 0 e 3 C) oppure collegare il cavo di comando all’unità (per le unità con controllo elettronico).
Attenzione! Per garantire il corretto intervento dei termostati di sicurezza, il riscaldatore va sempre
installato con il coperchio di ispezione rivolto verso l’alto.
The unit can be equipped with an electric channel heater that can be installed as an antifreeze protection.
Due to the variety of types existing, detailed installation instructions are supplied with the heater itself. Below are
some indications.
Antifreeze feature: in this case the heater, in winter when the external temperature drops below 0°C, has the function
of heating the incoming air on the unit in order to avoid the formation of ice on the exchange pack of the unit.
Installation:
• mount the heater on the “Renewal” duct (external air intake);
• connect the heater to the mains;
• set the regulation thermostat between 0 and 3°C (if the heating element has 2 stages set a thermostat between -2
and 0°C and the other between 0 and 3°C) or connect the control cable to the unit (for units with electronic control).
Attention! To ensure the correct operation of the safety thermostats, the heater must always be installed with the
inspection cover facing upwards.