Time parameter configuration
Installer Manual -
TP8-96 VIDEO
4-2
z
Disarming confirmation time (mm:ss)
Programming of the maximum time for confirmation of disarming (from 0 to 59 minutes and 59 seconds) by
transponder or wireless key. If no valid code is entered within the programmed disarming confirmation time,
disarming is ignored and a silent hold-up alarm is released. The alarm call cycle is executed but acoustic signaling
is not activated.
Warning: The confirmation of disarming is accepted only by entering a user code on the console.
If programmed accordingly, even quick disarming is accepted.
From 0 to 59 minutes and 59 seconds
z
Channel delay (mm:ss)
Permits programming of the interval between the detection of an alarm and the activation of the telephone channels
(alarm call cycle).
From 0 to 59 minutes and 59 seconds
z
Siren delay (mm:ss)
Permits programming of the interval between the detection of an alarm and the activation of the sirens.
From 0 to 59 minutes and 59 seconds
Warning: The siren delay is deducted from the programmed alarm time.
z
Alarm time (mm:ss)
Defines the duration of alarm signaling (indoor-outdoor-wireless sirens/LED) for program alarm.
From 0 to 59 minutes and 59 seconds
z
Tamper alarm time (mm:ss)
Defines the duration of alarm signaling (indoor-outdoor-wireless sirens/LED) for tamper alarm.
The tamper alarm is released by opening of tamper input (ZT) or if one of the peripherals connected on the serial bus
is sabotaged.
From 0 to 59 minutes and 59 seconds
z
Technical alarm time (mm:ss)
Defines the duration of signaling (indoor-outdoor-wireless sirens/LED) for technical alarm.
The technical alarm is released upon opening of a detector/contact connected to the technical zone.
From 0 to 59 minutes and 59 seconds
z
Hold-up alarm time (mm:ss)
Defines the duration of signaling (indoor-outdoor-wireless sirens/LED) for hold-up alarm.
The hold-up alarm is released upon opening of a detector/contact connected to the hold-up zone.
From 0 to 59 minutes and 59 seconds
z
End of by-pass warning (mm:ss)
Defines the duration of the warning (buzzer of the consoles) prior to end of by-pass.
From 0 to 59 minutes and 59 seconds
z
Automatic arming warning (mm:ss)
Defines the duration of the warning (buzzer of the consoles) prior to automatic arming.
Warning: The programmed time delays the moment of arming.
From 0 to 59 minutes and 59 seconds
z
Antimasking (antijamming) delay (mm:ss)
Defines the delay of signaling for jamming.
An alarm is released if the control panel detects a jamming signal with the same frequency as that of the wireless
detectors which persists during a time superior to the programmed antimasking delay.
From 0 to 59 minutes and 59 seconds
z
Delay power failure alarm (hh:mm)
Defines the delay of signaling between the detection of power failure alarm (230V) and the alarm release (activation
of the alarm call cycle).
This function permits to delay the alarm calls for power failure in order to avoid false alarms in case of voltage drop or
temporary disconnection for maintenance etc.
If the mains voltage is missing for time superior to the programmed power failure alarm delay, alarm is released.
If the mains voltage is missing for time inferior to the programmed power failure alarm delay, alarm is not released.
In both cases, the events are stored in the event log.
From 0 to 23 hours and 59 minutes
z
Max. duration of by-pass (hh:mm)
Defines the maximum duration of by-pass.
From 0 to 23 hours and 59 minutes
z
Supervision interval (hh:mm)
Defines the maximum interval between the test transmissions of the wireless devices.
The supervision alarm is released if one of the wireless devices managed by the control panel does not communicate
with the control panel for a time superior to the programmed supervision interval.
From 2 to 23 hours and 59 minutes
Press:
z
OK
to confirm and quit
z
Abandon
to quit without saving
Summary of Contents for TP8-96
Page 4: ...IV Installer Manual TP8 96 VIDEO...
Page 16: ...Introduction to the TP8 96 VIDEO system Installer manual TP8 96 VIDEO 1 10...
Page 17: ...TP8 96 VIDEO Installer manual Introduction to the TP8 96 VIDEO system 1 11...
Page 44: ...Zoneconfiguration Installer Manual TP8 96 VIDEO 2 26...
Page 60: ...Telephonesectionconfiguration Installer Manual TP8 96 VIDEO 3 16...
Page 66: ...Telephonesectionconfiguration Installer Manual TP8 96 VIDEO 3 22...
Page 76: ...Timeparameterconfiguration Installer Manual TP8 96 VIDEO 4 10 Test call server Access periods...
Page 88: ...Accessconfiguration Installer Manual TP8 96 VIDEO 5 12...
Page 102: ...Special procedures Installer Manual TP8 96 VIDEO A 2...
Page 111: ...TP8 96 VIDEO Installer Manual Special procedures A 11 ELECTRONIC BOARD...
Page 113: ...TP8 96 VIDEO Installer Manual Special procedures A 13 SYSTEM...
Page 114: ...Special procedures Installer Manual TP8 96 VIDEO A 14 CAMERA CONNECTION...
Page 115: ...TP8 96 VIDEO Installer Manual Special procedures A 15 SUPPLY BY TERMINALS...
Page 116: ...Special procedures Installer Manual TP8 96 VIDEO A 16 SUPPLY BY CABLES SPLITTER...
Page 117: ...TP8 96 VIDEO Installer Manual Special procedures A 17...