Controlling with External Analog & Contact Signals
136
TRIP Operation with Isolated External Contacts
* This function can be set for isolation-option-featured type "model name with I" only.
The input for this machine can be shut off (switching stop by setting) using output from small capacity contacts or
photocouplers.
Use a photocoupler or a small signal relay or switch with a minimum contact capacity of 5V, 2.5mA.
Connecting
Wire the cables to the isolated control connector (accessory) terminals No. 9 and 10.
By connecting the external control connector (accessory) terminals No. 11 and 24, contact-b operation can be
performed.
TRIP operation with insulation external contacts
11
24
9
10
a Case of contact a operation selection (external control connector
No.11, No.24 not connected)
Closed: TRIP
b Case of contact a operation selection (external control connector
No.11, No.24 connected)
open: TRIP
Insulation Control Connector
Photocupler or Contact
Twisted-Pair Wire
External Control Connector
You can choose TRIP operation by short circuit (make) of contact a and TRIP
operation by opening (break) of contact b.
MEMO
Not suited for power contacts such as main contacts for
electromagnetic contactors or power relays.
!
CAUTION
The commons for contact point signal (external control connector No. 23,24) is internally
connected to the minus side of the output terminal.
Isolation for the wire connecting to the external control should be more than the relative ground
voltage of this product.
Otherwise, the user may receive electric shock.
!
CAUTION
Summary of Contents for HX-S-G4 Series
Page 157: ...Special Loads 157 This page is blank...
Page 161: ...Maintenance 161 This page is blank...
Page 197: ...Specifications 197 External Diagrams 1 HX S 030 200G4 F I...
Page 198: ...Specifications 198 2 HX S 030 400G4 F I...
Page 199: ...Specifications 199 3 HX S 060 100G4 F I...
Page 200: ...Specifications 200 4 HX S 060 200G4 F I...
Page 201: ...Specifications 201 5 HX S 0500 12G4 F I...
Page 202: ...Specifications 202 6 HX S 0500 24G4 F I...
Page 203: ...Specifications 203 7 HX S 01000 6G4 F I...