Using in Series/Parallel Operation
125
Calibrating Slave Unit Output Settings
Calibrate the Slave unit to match the Slave’s output voltage in series operation with the Master’s voltage.
Preparation
The following measuring device is required for calibration.
Voltage Measuring Digital Multimeter
2 devices
No. of Display Digits: 5 1/2 or more Display Accuracy : 0.005% or more
* (30V/60V Type
:
Equipped with a measuring range from 1mV to 100V)
(500V Type
:
Equipped with a measuring range from 1mV to 1000V)
Offset/Full Scale Calibration of Slave Unit Output Voltage
1. Disconnect the load wires and the remote sensing
wires. Connect the digital multimeter to the output
terminal of the Master and the Slave respectively.
Turn the POWER switch ON and OUTPUT OFF in
advance.
+
-
V
+
-
+
-
V
+
-
Slave Unit
Master
Digital Multimeter
Digital Multimeter
2. At the Master, set the constant voltage setting
value to [ xV ] and the constant current setting
value to [ yA ] and set the output to ON.
30V Type
60V Type
500V Type
[xV]
0.01V
0.01V
0.1V
[yA]
1.0A
1.0A
0.1A
On how to set, see Operating as Constant Voltage
Power Supply under Basic Operations.(page27)
3. Press the FUNC. key of the Slave.
4. Turn the VOLTAGE dial of the Slave unit to display
the setting item number 37 in the Number Display
(voltage).
* At that time, turn off the Number Display (current).
5. Adjust the CURRENT dial of the Slave so that the
display of the digital multimeter for output voltage
measurement is the same as the display of the
digital multimeter for output voltage measurement.
6. Press the FUNC. key of the Slave unit to set the
offset calibration value of output voltage setting.
7. At the Master, set the constant voltage setting
value to [ xV ] and the constant current setting
value to [ yA ] and set the output to ON.
30V Type
60V Type
500V Type
[xV]
30.00V
60.00V
500.0V
[yA]
1.0A
1.0A
0.1A
On how to set, see Operating as Constant Voltage
Power Supply under Basic Operations. (Page27)
Summary of Contents for HX-S-G4 Series
Page 157: ...Special Loads 157 This page is blank...
Page 161: ...Maintenance 161 This page is blank...
Page 197: ...Specifications 197 External Diagrams 1 HX S 030 200G4 F I...
Page 198: ...Specifications 198 2 HX S 030 400G4 F I...
Page 199: ...Specifications 199 3 HX S 060 100G4 F I...
Page 200: ...Specifications 200 4 HX S 060 200G4 F I...
Page 201: ...Specifications 201 5 HX S 0500 12G4 F I...
Page 202: ...Specifications 202 6 HX S 0500 24G4 F I...
Page 203: ...Specifications 203 7 HX S 01000 6G4 F I...