powEr SUpply wpl 13/18/23 E/cool
Power supply
You may need to notify your local
power supply company of the heat
pump connection.
All electrical installation work,
particularly earthing measures, must
be carried out in accordance with
local and national regulations and
the requirements of your local power
supply company. the connection must
comply with the power connection
diagram. For this, also observe the
installation instructions for the heat
pump manager wPM ii.
For external installation
Use only cables suitable for external
use to VDe 0100 [or local regulations].
route such cables through a conduit
(protective pipe); entry into the heat
pump only from below.
For internal installation
route the cables through the
installation aperture in the side of the
heat pump.
Electrical specification of the heat pump
Heat pump
Power
consumption
kw
Max. operating
current
A
starting
current r start
A
Power cable
mm²
Fuse
protection
A
wPl 13 e
2.7
8.0
24
5 x 2.5 *
C 16A all poles
wPl 18 e
3.5
10.6
26
5 x 2.5 *
C 16A all poles
wPl 23 e
3.9
11.4
29
5 x 2.5 *
C 16A all poles
* Cable cross-section acc. to type of routing (observe VDe 0298-4 [or local regulations])
WPL
3/n/Pe
230V ~ 50Hz
Domestic
electricity meter
Control phase l
w/o power-oFF
period
Control phase l´
with power-oFF
period
3/n/Pe
400V ~ 50Hz
Heat pump
electricity meter
M1 = Circulation pump (max. 2A gl)
WPL + WPIC
3/n/Pe
230V ~ 50Hz
Domestic
electricity meter
Control phase l
w/o power-oFF
period
Control phase l´
with power-oFF
period
3/n/Pe
400V ~ 50Hz
Heat pump
electricity meter
impuls
Pulse input wP
l
Power supply
t (Hrl)
temperature sensor heat pump return ZKP
DHw circulation pump
Fühler 1 temp. sensor, heat meter/solar
eVU
enable signal
Fühler 2 temp. sensor, heat meter/solar
HKP
Heating circuit pump
t (ww)
temperature sensor, DHw
2.we
Heat source 2
t(2.we) temperature sensor heat source 2
M(A)
Mixer open
t(A)
outside temperature sensor
M(Z)
Mixer closed
t(MK)
temperature sensor, mixer circuit
MKP
Mixer circuit pump
Fern1
remote control
KoKP
Collector circuit pump
Fern3
remote control
Summary of Contents for Heat pumps
Page 97: ...97 www stiebel eltron COM Notes ...
Page 110: ...110 www stiebel eltron COM Notes ...
Page 116: ...116 www stiebel eltron COM Notes ...
Page 124: ...124 www stiebel eltron COM Notes ...
Page 182: ...182 www stiebel eltron COM Notes ...
Page 183: ...183 www stiebel eltron COM Accessories for heating heat pumps ...