HEatIng SyStEm connEctIon wpl 10
Heating system connection
install the heat utilisation system
(wnA) in accordance with the design
documentation. For standard heating
systems integrate the heat pump into
the water side according to standard
circuits (see appendix). Prior to
connecting the heat pump, check
the heating system for leaks, flush it
thoroughly, fill and vent it thoroughly.
Check the correct connection of the
heating flow and return. Flexible
pressure hoses are recommended to
reduce structure-borne noise on the
water side. the required circulation
pump and the pipe cross-section can
be determined from the table below.
Fit thermal insulation in accordance
with local regulations. when using
the compact installation wPKi 5, use
the following circulation pumps: see
table.
Circulation pump for the heat pump with WPKI 5
(between the heat pump and the buffer cylinder; max. pipe length 10 m)
Heat pump
Flow rate
m³/h
Pressure differential
hPa
Circulation pump
type
Copper pipe
Dn
wPl 10
1.0
200
UP 25 - 60
22 x 1.0
WPL with buffer cylinder SBP 700 and DHW heating
Summary of Contents for Heat pumps
Page 97: ...97 www stiebel eltron COM Notes ...
Page 110: ...110 www stiebel eltron COM Notes ...
Page 116: ...116 www stiebel eltron COM Notes ...
Page 124: ...124 www stiebel eltron COM Notes ...
Page 182: ...182 www stiebel eltron COM Notes ...
Page 183: ...183 www stiebel eltron COM Accessories for heating heat pumps ...