123
www.stiebel-eltron.CoM
cHEcklISt
Design/engineering and installation of brine | water heat pumps
what is the purpose of the heat pump?
what heat source supplies the heat pump?
How are the heating surfaces designed? low temperature heating systems are recommended.
what is the required heating output? Calculate the heat demand.
obtain permission from your power supply utility [if required].
Determine the operating mode of the heat pump according to the heating system.
How can the heat pump be integrated easily into the heating pipework?
should DHw be heated by the heating heat pump?
is a suitable location that is free from the risk of frost available for the installation of the heat pump?
where can the heat pump be located? Provide foundations.
How do i make the power connection?
observe general requirements and guidelines.
observe conditions on site.
Brine | water heat pump with geothermal collector
Must your local water board be notified?
is sufficient property available for the installation of a geothermal collector?
Can the geothermal collector be installed at a depth of 1.2 to 1.5 metres?
Can the pipe circles be split and buried equally?
Can the flow and return distributor be installed outside the building?
All lines and fittings/valves must be made from corrosion-resistant material.
Can the geothermal collector pipes be routed with a gradient to the distributor?
insulate the heat source lines inside the building with vapour diffusion-proof material.
First mix the brine concentrate with water, then fill the mixture into the heat source system.
Prior to commissioning, fill the system with brine and pressure test it.
Use only a circulation pump that is resistant to brine and condensate.
the brine increases the pressure drop. take this into consideration when sizing the pump.
the changes in volume require the installation of a brine resistant expansion vessel.
Brine | water heat pump with geothermal probes
is a permit required from your local water board?
is sufficient space available for the geothermal probe hole?
Can the probe lines to the distributor be split equally?
Can the flow and return distributor be installed outside the building?
All lines and fittings/valves must be made from corrosion-resistant material.
Can the geothermal probe pipes be routed with a gradient to the distributor?
insulate the heat source lines inside the building with vapour diffusion-proof material.
First mix the brine concentrate with water, then fill the mixture into the heat source system.
Prior to commissioning, fill the system with brine and pressure test it.
Use only a circulation pump that is resistant to brine and condensate.
the brine increases the pressure drop. take this into consideration when sizing the pump.
the changes in volume require the installation of a brine resistant expansion vessel.
Summary of Contents for Heat pumps
Page 97: ...97 www stiebel eltron COM Notes ...
Page 110: ...110 www stiebel eltron COM Notes ...
Page 116: ...116 www stiebel eltron COM Notes ...
Page 124: ...124 www stiebel eltron COM Notes ...
Page 182: ...182 www stiebel eltron COM Notes ...
Page 183: ...183 www stiebel eltron COM Accessories for heating heat pumps ...