228
www.stiebel-eltron.CoM
platE-typE HEat ExcHangEr
Heat exchanger
Accessories
Type
WT 10
WT 20
WT 30
WT 40
Part no.
07 06 33
07 06 34
07 10 91
22 93 38
Specification
Primary temperature
°C 60 > 52
60 > 52
60 > 52
60 > 52
secondary temperature
°C 55 < 45
55 < 45
55 < 45
55 < 45
Primary pressure drop
hPa 70
100
90
90
secondary pressure drop
hPa 50
70
60
60
Primary flow rate
m³/h 1.1
2.3
3.2
6.0
secondary flow rate
m³/h 0.9
1.9
2.5
4.8
output
kw 10
22
32
50
Weight and dimensions
Height
mm 304
304
304
304
width
mm 103
103
103
103
Depth
mm 65
102
140
280
weight
kg 2.8
4.4
6.0
14.0
Technical description:
Plate-type heat exchanger with thermal insulation for DHw heating. Comprises several
hard soldered stainless steel plates.
Inlet connector
for floorstanding DHw cylinder
for floorstanding stiebel eltron cylinder sb
l 302 – 402
602 – 1002
Part no.
07 29 97
07 29 98
Specification
DHw cylinder connection
inches G 1"
G 2"
inlet pipe connection
inches G 1"
G 1"
length of the inlet pipe
m 0.5
0.7
Technical description:
inlet pipe for feeding water from an external heat exchanger.
Effect of water-borne particles in DHW systems on copper-soldered plate-type heat
exchangers (water quality requirements / limits)
pH value
7 to 9
Free chlorine
< 0.5 ppm
so
4
< 100 ppm
Fe
< 0.5 ppm
HCo
3
- so
4
> 1
Mn
< 0.05 ppm
Ci
< 50 ppm
Co
2
< 10 ppm
Po
4
< 2 ppm
H
4
s
< 50 ppb
nH
3
< 0.5 ppm
Conductivity
> 50 us/cm,
wall temperature
< 80 °C
Additional factors with an influence on corrosion are water contamination, velocity,
contamination or deposits inside heat exchangers and mixing installations.
Summary of Contents for Heat pumps
Page 97: ...97 www stiebel eltron COM Notes ...
Page 110: ...110 www stiebel eltron COM Notes ...
Page 116: ...116 www stiebel eltron COM Notes ...
Page 124: ...124 www stiebel eltron COM Notes ...
Page 182: ...182 www stiebel eltron COM Notes ...
Page 183: ...183 www stiebel eltron COM Accessories for heating heat pumps ...