bUffEr cylIndEr Sbp 700 E, Sbp 700 E Sol
Buffer cylinder 700 litres
for heating heat pumps
Type
SBP 700 E
SBP 700 E SOL
Part no.
18 54 59
18 54 60
Specification
Max. operating pressure
bar 3
3
test pressure
bar 4
4
water capacity
l 700
700
Connector
inches G 2" (male)
G 2" (male)
Female connection for booster heater
inches G 1½"
G 1½"
Female connection for air vent valve
inches r ¾"
r ¾"
Female connection with protective pipe inches G ½"
G ½"
indirect coil connections
inches –
G 1"
indirect coil surface area
m² –
2.0
Weight and dimensions
Height
mm 1890
1890
Diameter incl. thermal insulation
mm 910
910
thermal insulation thickness
mm 80
80
Height when tilted
mm 2000
2000
weight
kg 145
176
Technical description SBP 700 E:
Cylinder for hydraulic separation of the heat pump and heating circuit flow. it is designed
to provide system separation, to extend the heat pump runtimes and, to an extent, to
bridge power-oFF periods. the 80 mm thermal insulation, as directly applied PU foam
insulation, ensures especially low heat losses and is protected with an easy care plastic
jacket. A sensor well is provided for connecting the lower sensor. the thermal insulation
can be removed from the sides to enable the transportation of the cylinder through
doorways as narrow as 770 mm.
Technical description SBP 700 E SOL:
Cylinder for the hydraulic separation of the heat pump and heating circuit flow, with an
additional smooth tube indirect coil for connecting, for example, solar thermal systems
into conventional heating systems. it is designed to provide system separation, to extend
the heat pump runtimes and, to an extent, to bridge power-oFF periods. the 80 mm
thermal insulation, as directly applied PU foam insulation, ensures especially low heat
losses and is protected with an easy care plastic jacket. the thermal insulation can be
removed from the sides to enable the transportation of the cylinder through doorways as
narrow as 770 mm. A sensor well is provided for connecting the lower sensor.
Buffer cylinder SBP 700 E / SOL
Position list
1
Connector G 2"
Heating flow
2
Connector G 2"
Heat pump flow
3
Connector G 2"
Heating return
4
Connector G 2"
Heat pump return
5
Connector G½"
with sensor well
6
Connector G1½"
for bGC
7
Connector r¾"
for air vent valve
8
Connector G1½"
Heat exchanger flow
9
Connector G1½"
Heat exchanger return
Dimensions in mm
Summary of Contents for Heat pumps
Page 97: ...97 www stiebel eltron COM Notes ...
Page 110: ...110 www stiebel eltron COM Notes ...
Page 116: ...116 www stiebel eltron COM Notes ...
Page 124: ...124 www stiebel eltron COM Notes ...
Page 182: ...182 www stiebel eltron COM Notes ...
Page 183: ...183 www stiebel eltron COM Accessories for heating heat pumps ...