Type
WPL 13 E/cool
WPL 18 E/cool
WPL 23 E/cool
Part no. standard appliance e
22 77 56
22 77 57
22 77 58
Part no. standard appliance cool
22 34 00
22 34 01
22 34 02
Part no. casing (external installation)
07 44 13
07 44 13
07 44 13
Part no. casing (internal installation)
07 44 12
07 44 12
07 44 12
Specification
Application limits wQA
°C -20 to +40
Flow temperature wnA
°C +15 to +60
Air flow rate wQA
m³/h 3200
3500
3500
external static pressure differential
Pa 100
100
100
Flow rate, heating side
m³/h 1.50
2.00
2.80
Pressure diff., heating side
hPa 105
145
190
Heating flow/return connection
inches G 1¼" (male)
Air hose connection
mm 721 x 248 oval
721 x 248 oval
721 x 248 oval
refrigerant
r407C
Fill weight
kg 5.9
5.9
5.9
Electrical details
Compressor power supply connection
n x mm² 5 x 2.5 cable cross-section acc. to type of routing (observe VDe 0298-4)
booster heater power supply connection
n x mm² 5 x 2.5 cable cross-section acc. to type of routing (observe VDe 0298-4)
Control cable
n x mm² 5 x 1.5
bUs cable
n x mm² J-Y (st) 2 x 2 x 0.8
Fuse - compressor
A C 16A all poles
electrical booster heater fuse
A C 16A
Control circuit fuse
A C 16A
Protection en 60529
iP 14?b
Voltage/frequency load
V/Hz 3/Pe ~ 400 V 50 Hz
booster heater connection
V/Hz 3/n/Pe ~ 400 V 50 Hz, 8.8 kw
Voltage/frequency control
V/Hz 1/n/Pe ~ 230 V / 50 Hz
starting current
A <30
<30
<30
Weight and dimensions
H x w x D (standard appliance)
mm 1116 x 1182 x 784
H x w x D (external installation)
mm 1434 x 1240 x 1280
H x w x D (internal installation)
mm 1182 x 1240 x 800
weight (standard appliance)
kg 210
220
225
total weight (external/internal)
kg 240/220
250/230
255/235
Other model characteristics
Corrosion protection
zinc-plated
Compliant with safety regulations
UVV/VDe/Gs
external sound power level
db(A) 65
external installation with sound insulation (accessory)
db(A) 63
internal sound power level
db(A) 56/62
57/62
58/62
sound pressure level at a distance of 5 m
db(A) 43
Output details, heating
Air temperature
°C –7
+2
+10
–7
+2
+10
–7
+2
+10
Flow temperature
°C +35
+35
+35
+35
+35
+35
+35
+35
+35
Heating output
kw 6.6
8.1
9.5
9.6
11.3
13.3
13.0
14.8
17.8
Power consumption
kw 2.2
2.4
2.3
3.0
3.0
2.9
4.2
4.2
4.2
CoP
ε 3.0
3.4
4.1
3.2
3.7
4.6
3.1
3.5
4.2
temperature differential at A2/w35
K 4.5
4.5
4.5
Output details cooling capacity
Air temperature
°C +30
+30
+30
+30
+30
+30
+30
+30
+30
Flow temperature
°C +7
+15
+20
+7
+15
+20
+7
+15
+20
Cooling capacity
kw 7.0
8.6
10.1
9.7
12.1
13.9
12.7
16.0
17.6
Power consumption
kw 2.5
2.8
3.0
3.5
3.9
4.2
5.5
6.1
6.4
CoP
ε 2.8
3.1
3.4
2.8
3.1
3.3
2.3
2.6
2.8
Summary of Contents for Heat pumps
Page 97: ...97 www stiebel eltron COM Notes ...
Page 110: ...110 www stiebel eltron COM Notes ...
Page 116: ...116 www stiebel eltron COM Notes ...
Page 124: ...124 www stiebel eltron COM Notes ...
Page 182: ...182 www stiebel eltron COM Notes ...
Page 183: ...183 www stiebel eltron COM Accessories for heating heat pumps ...