![STIEBEL ELTRON Heat pumps Technical Manual Download Page 77](http://html1.mh-extra.com/html/stiebel-eltron/heat-pumps/heat-pumps_technical-manual_1376699077.webp)
77
www.stiebel-eltron.CoM
powEr SUpply wpl 10
Power supply
You may need to notify your local
power supply company of the heat
pump connection.
All electrical installation work,
particularly earthing measures, must
be carried out in accordance with
local and national regulations and
the requirements of your local power
supply company. the connection must
comply with the power connection
diagram. For this, also observe the
installation instructions for the heat
pump manager wPM ii.
For external installation
Use only cables suitable for external
use to VDe 0100 [or local regulations].
route such cables through a conduit
(protective pipe); entry into the heat
pump only from below.
For internal installation
route the cables through the
installation aperture in the side of the
heat pump.
Electrical specification of the heat pump
Heat pump
Power
consumption
kw
Max. operating
current
A
starting
current r start
A
Power cable
mm²
Fuse
protection
A
wPl 10
2.2
6.0
<25
5 x 2.5 *
C 16A all poles
* Cable cross-section acc. to type of routing (observe VDe 0298-4 [or local regulations])
WPL
3/n/Pe
230V ~ 50Hz
Domestic
electricity meter
Control phase l
w/o power-oFF
period
Control phase l´
with power-oFF
period
3/n/Pe
400V ~ 50Hz
Heat pump
electricity meter
M1 = Circulation pump (max. 2A gl)
WPL IK
3/n/Pe
230V ~ 50Hz
Domestic
electricity meter
Control phase l
w/o power-oFF
period
Control phase l´
with power-oFF
period
3/n/Pe
400V ~ 50Hz
Heat pump
electricity meter
impuls
Pulse input wP
l
Power supply
b2
temperature sensor heat pump return KoKP
Collector circuit pump
Fühler 1 temp. sensor, heat meter/solar
MKP
Mixer circuit pump
Fühler 2 temp. sensor, heat meter/solar
eVU
enable signal
t (ww)
temperature sensor, DHw
Pumpe Power supply
t(2.we) temperature sensor heat source 2
M(A)
Mixer open
t(A)
outside temperature sensor
M(Z)
Mixer closed
t(MK)
temperature sensor, mixer circuit
HKP
Heating circuit pump
Fern1
remote control
2.we
Heat source 2
Fern3
remote control
ZKP
DHw circulation pump
Summary of Contents for Heat pumps
Page 97: ...97 www stiebel eltron COM Notes ...
Page 110: ...110 www stiebel eltron COM Notes ...
Page 116: ...116 www stiebel eltron COM Notes ...
Page 124: ...124 www stiebel eltron COM Notes ...
Page 182: ...182 www stiebel eltron COM Notes ...
Page 183: ...183 www stiebel eltron COM Accessories for heating heat pumps ...