Application Macros
15-8
605C Frequency Inverter
Macro 3: Raise/Lower Trim
This macro provides a raise/lower (push button) interface for an additional Setpoint Trim. The Setpoint is
derived from the sum of ANALOG INPUT 1, ANALOG INPUT 2 and the output of the raise/lower ramp.
This ramp is controlled by the 3 digital inputs RAISE INPUT, LOWER INPUT and RESET of the
RAISE/LOWER function block.
The raise/lower trim is restricted to be +/- 10.00%. This limit is set by the MIN VALUE and MAX VALUE
parameters in the RAISE/LOWER function block.
Note that the raise/lower ramp output is automatically preserved in non-volatile memory during a
power-down
.
Terminal
Name
Purpose
Comment
1
ANALOG INPUT 1
Setpoint
0V = 0%, 10V = 100%
2
ANALOG INPUT 2
Setpoint Trim
0V = 0%, 10V = 100%
6
ANALOG OUTPUT 1
Ramp Output
Absolute Speed Demand,
0V = 0%, 10V = 100%
13
DIGITAL INPUT 1
Run
24V = Run
14
DIGITAL INPUT 2
Raise
24V = Ramp Up
15
DIGITAL INPUT 3
Lower
24V = Ramp Down
16
DIGITAL INPUT 4
External Trip
0V = Trip
(connect to terminal 18)
17
DIGITAL INPUT 5
Reset
24V = Reset and Hold Raise
Lower
21, 22
DIGITAL OUTPUT 1
Health
0V = Tripped, i.e. not healthy
23, 24
DIGITAL OUTPUT 2
Running
0V = Stopped, 24V = Running
The Operator Menu System for Macro 3
The default Operator menu system is shown below.
SETPOINT (REMOTE)
SPEED DEMAND
DRIVE FREQUENCY
MOTOR CURRENT
LOAD
DC LINK VOLTS
CURRENT LIMITING
ENTER PASSWORD
STARTUP SCREEN
Summary of Contents for 605C
Page 16: ...1 4 Getting Started 605C Frequency Inverter ...
Page 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Page 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Page 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Page 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Page 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Page 212: ...13 6 Application Notes 605C Frequency Inverter ...
Page 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Page 236: ......