Programming Your Application
6-61
605C Frequency Inverter
SLIP COMP
The slip compensation function block
allows the Inverter to maintain motor
speed in the presence of load
disturbances.
Functional Description
Based on the rated speed, the no load speed and the rated load of the motor, the slip
compensation block adjusts the demand frequency to compensate for any speed slippage
resulting from the load.
MMI Menu Map
1
SETUP PARAMETERS
2
FUNCTION BLOCKS
3
MOTOR CONTROL
4
SLIP COMP
SLIP ENABLE
NAMEPLATE RPM
MOTOR POLES
SLIP MOTOR LIMIT
SLIP REGEN LIMIT
SLIP ACTIVE
SLIP COMP
SLIP ACTIVE [762]
–
FALSE
FALSE – [ 82]
ENABLE
–
** 1400 n/min
–
[ 83]
NAMEPLATE RPM
–
4
–
[ 84]
MOTOR POLES
–
** 150.0 n/min
–
[ 85]
MOTORING LIMIT
–
** 150.0 n/min
–
[ 86]
REGEN LIMIT
–
Parameter Descriptions
ENABLE
Range: FALSE / TRUE
For the slip compensation to be operational this must be TRUE.
NAMEPLATE RPM
Range: 0 to 28800 n/min
This is the rated speed of the motor at rated load.
MOTOR POLES
Range: Enumerated - see
below
The number of motor poles. The values that this parameter may take are:
Enumerated Value
:
Number of poles
0 : 2
1 : 4
2 : 6
3 : 8
4 : 10
5 : 12
MOTORING LIMIT
Range: 0.0 to 600.0 n/min
The maximum trim that will be produced by the slip compensation block when the motor is
driving the load (motoring).
REGEN LIMIT
Range: 0.0 to 600.0 n/min
The maximum trim that will be produced by the slip compensation block when the motor is
being driven by the load, (regenerating).
SLIP ACTIVE
Range: FALSE / TRUE
Indicates when Slip Compensation is being applied.
Speed
Rated
Speed
No Load Speed
(synchronous speed)
Rated
Torque
Torque
Summary of Contents for 605C
Page 16: ...1 4 Getting Started 605C Frequency Inverter ...
Page 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Page 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Page 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Page 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Page 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Page 212: ...13 6 Application Notes 605C Frequency Inverter ...
Page 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Page 236: ......