10-2
Parameter Specification
605C Frequency Inverter
Specification Table: Tag Number Order
Tag
(MMI) Name
Block
Type
Range
ID
Notes
1
LANGUAGE
OP STATION
ENUM
0 : ENGLISH
1 : DEUTSCH
2 : FRANCAIS
3 : ESPANOL
01
3
VIEW LEVEL
OP STATION
ENUM
0 : OPERATOR
1 : BASIC
2 : ADVANCED
3 : RESERVED
4 : ENGINEERING
03
4
ACTIVE TRIPS
TRIPS STATUS
WORD
0000 to FFFF
04
Output
5
TRIP WARNINGS
TRIPS STATUS
WORD
0000 to FFFF
05
Output
6
FIRST TRIP
TRIPS STATUS
ENUM
0 : NO TRIP
1 : LINK OVERVOLTS
2 : LINK UNDERVOLT
3 : OVERCURRENT
4 : HEATSINK TEMP
5 : EXTERNAL TRIP
6 : INPUT 1 BREAK
7 : INPUT 2 BREAK
8 : MOTOR STALLED
9 : I*T TRIP
10 : BRAKE RESISTOR
11 : BRAKE SWITCH
12 : OP STATION
13 : LOST COMMS
14 :
15 :
16 :
17 : MOTOR TEMP
18 : CURRENT LIMIT
19 : SHORT CIRCUIT
20 : 24V FAILURE
21 : LOW SPEED I
22 : PHASE FAIL
06
Output
7
ENTER PASSWORD
PASSWORD
WORD
0000 to FFFF
07
1, 5, 6
8
CHANGE PASSWORD
PASSWORD
WORD
0000 to FFFF
08
5, 6
12
AIN 1 BREAK ENBL
ANALOG INPUT 1
BOOL
FALSE / TRUE
0c
13
AIN 1 TYPE
ANALOG INPUT 1
ENUM
0 : 0..+10 V
1 : +2..+10 V
2 : 0..+5 V
3 : +1..+5 V
4 : -10..+10 V
5 : 0..20 mA
6 : 4..20 mA
7 : 20..4 mA
8 : 20..0 mA
0d
7
14
AIN 1 SCALE
ANALOG INPUT 1
INT
-300.00 to 300.00 %
0e
15
AIN 1 OFFSET
ANALOG INPUT 1
INT
-300.00 to 300.00 %
0f
16
AIN 1 VALUE
ANALOG INPUT 1
INT
xxx.xx %
0g
Output
17
AIN 1 BREAK VAL
ANALOG INPUT 1
INT
-300.00 to 300.00 %
0h
18
AIN 1 BREAK
ANALOG INPUT 1
BOOL
FALSE / TRUE
0i
Output
21
AIN 2 BREAK ENBL
ANALOG INPUT 2
BOOL
FALSE / TRUE
0l
22
AIN 2 TYPE
ANALOG INPUT 2
ENUM
Same as tag 13
0m
7
23
AIN 2 SCALE
ANALOG INPUT 2
INT
-300.00 to 300.00 %
0n
24
AIN 2 OFFSET
ANALOG INPUT 2
INT
-300.00 to 300.00 %
0o
25
AIN 2 VALUE
ANALOG INPUT 2
INT
xxx.xx %
0p
Output
26
AIN 2 BREAK VAL
ANALOG INPUT 2
INT
-300.00 to 300.00 %
0q
27
AIN 2 BREAK
ANALOG INPUT 2
BOOL
FALSE / TRUE
0r
Output
Summary of Contents for 605C
Page 16: ...1 4 Getting Started 605C Frequency Inverter ...
Page 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Page 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Page 66: ...5 16 The Operator Station 605C Frequency Inverter ...