Programming Your Application
6-43
605C Frequency Inverter
OPERATOR MENU
This function block is used to customise the
Operator menu, the default menu displayed
at start-up.
By entering parameter tag numbers, you
can assign which parameters will be in the
menu, and their order of appearance.
This function block also assigns the
parameter that will be displayed
immediately after the power-up screen.
Functional Description
The Operator menu consists of up to 16 entries, including the Startup screen. OP MENU 1 (not
included in the function block) is fixed to always be the active setpoint or speed demand. The
remaining 14 entries (OP MENU 2 to OP MENU 15 ) may be customised to show any
parameter in the Inverter.
The default (Macro 1) tags for the OPERATOR menu display the following parameters:
255: SPEED DEMAND
591: DRIVE FREQUENCY
67: MOTOR CURRENT
72: LOAD
75: DC LINK VOLTS
370: CURRENT LIMITING
Also, the Startup screen is selected to display OPERATOR MENU 1, which is fixed to display
the SETPOINT parameter.
MMI Menu Map
1
SETUP PARAMETERS
2
FUNCTION BLOCKS
3
MENUS
4
OPERATOR MENU
STARTUP SCREEN
OP MENU 2
OP MENU 3
OP MENU 4
OP MENU 5
OP MENU 6
OP MENU 7
OP MENU 8
OP MENU 9
OP MENU 10
OP MENU 11
OP MENU 12
OP MENU 13
OP MENU 14
OP MENU 15
OPERATOR MENU
1 – [93]
STARTUP SCREEN
–
255
–
[626] OP MENU 2
–
591
–
[627] OP MENU 3
–
67
–
[628] OP MENU 4
–
72
–
[629] OP MENU 5
–
75
–
[630] OP MENU 6
–
370
–
[631] OP MENU 7
–
0
–
[632] OP MENU 8
–
0
–
[633] OP MENU 9
–
0
–
[634] OP MENU 10
–
0
–
[635] OP MENU 11
–
0
–
[636] OP MENU 12
–
0
–
[637] OP MENU 13
–
0
–
[638] OP MENU 14
–
0
–
[639] OP MENU 15
–
Parameter Descriptions
STARTUP SCREEN
Range: 0 to 15
Selects which of the parameters will be displayed immediately after the startup screen. The
range refers to the OPERATOR MENU numbers below. Whichever parameter is selected by the
relevant OPERATOR MENU will be displayed as the Startup screen.
•
A value of 0 selects the Welcome screen to be displayed (refer to CONFIGURATION ID
parameter in the OP STATION function block).
•
A value of 1 selects the REMOTE SETPOINT or LOCAL SETPOINT parameter to be
displayed.
•
A value of 2 to 15 selects the corresponding entry in the Operator menu to be displayed.
OP MENU 2 to 15
Range: See the table below
Selects a parameter screen for the OPERATOR menu. Enter the parameter’s tag number. Each
entry in the menu may be set to the tag number of any visible parameter within the Inverter.
There are also four special tag numbers:
•
0
Prevents this entry from displaying in the Operator menu
•
1000
Displays the current setpoint (Local, Remote, Jog)
•
1001
Displays the CUSTOM SCREEN 1
•
1002
Displays the CUSTOM SCREEN 2
Summary of Contents for 605C
Page 16: ...1 4 Getting Started 605C Frequency Inverter ...
Page 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Page 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Page 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Page 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Page 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Page 212: ...13 6 Application Notes 605C Frequency Inverter ...
Page 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Page 236: ......