12-12
Certification for the Inverter
605C Frequency Inverter
Product Specific Standard EN61800-3
Unit used as
Relevant Apparatus
Unit used as a
Component
Assuming installation to EMC instructions in this manual
“Filter” refers to a specified external filter.
filter
(EMC
compliance)
no filter
filter
(EMC
compliance
may be
applied for)
no filter
Installation
Sales
Performance Required
enclosure
enclosure
enclosure
enclosure
FIRST
ENVIRONMENT
Unrestricted
Sales
Distribution:
Sales is not
dependent on
Radiated
RF Emission
Class A performance
models rated >25A
Class B performance
models rated <25A *
✓
✓
✓
✓
Environment
includes domestic
premises
the EMC
competence of
the customer
Conducted
RF Emission
Class A performance
models rated >25A
Class B performance
models rated <25A **
✓
✓
Includes
commercial and
industrial
installations
Restricted
Sales
Distribution:
Sales restricted
to customers
Radiated
RF Emission
Class A performance
(all models)
✓
✓
✓
✓
supplied directly
from public
electricity supply
which also supplies
domestic
with technical
competence in
EMC
requirements
of drives
Conducted
RF Emission
Class A performance
(all models)
✓
✓
premises
Immunity
•
See below for
referenced standards
✓
✓
✓
✓
SECOND
ENVIRONMENT
All environments
except domestic
premises.
All commercial,
light industry and
industrial
installations,
supplied from an
RF Emission
EMC measures do not
have to be
implemented
If interference in a
neighbouring
installation occurs, the
operator is responsible
for taking measures to
prevent interference.
In this case the
required emission
levels must be
adhered to at the point
of supply to the
affected neighbouring
installation
✓
✓
✓
✓
intermediate
transformer or
directly from public
electricity supply,
which do not supply
domestic premises
.
Immunity
•
See below for
referenced standards.
✓
✓
✓
✓
* Cubicle mount only ** Maximum 5m shielded motor cable only
•
Standards for Immunity:
IEC1000-4-2
Electrostatic discharge (e.g. from electrostatically charged
persons
IEC1000-4-9
Pulsed magnetic field
IEC1000-4-3/6
Electromagnetic fields (e.g. from portable telephones
IEC1000-4-11
Voltage Dips Short Interruptions and
voltage variations
IEC1000-4-4
Fast electrical transients (burst) (e.g. from opening
contacts in inductive circuits)
IEC1000-4-13*
Harmonics and interharmonics
IEC1000-4-5
Voltage surges (e.g. on local lightning strikes).
IEC1000-4-14*
Mains Voltage Fluctuations
IEC1000-4-8
Power Frequency Magnetic Field
IEC1000-4-16
Power Frequency Common mode
IEC1000-4-27*
Unbalance
Summary of Contents for 605C
Page 16: ...1 4 Getting Started 605C Frequency Inverter ...
Page 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Page 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Page 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Page 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Page 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Page 212: ...13 6 Application Notes 605C Frequency Inverter ...
Page 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Page 236: ......