2-2
An Overview of the Inverter
605C Frequency Inverter
Control Features
The 605C Inverter is fully-featured when controlled using the optional Operator Station (or a
suitable PC programming tool).
The `General’ control features below are not available when the unit is controlled using the
analog and digital inputs and outputs.
General
Output Frequency
Selectable 0-120Hz, 240Hz or 480Hz
Switching Frequency
Constant Torque
: selectable 3kHz or 6kHz depending on
power rating
Quadratic Torque
: 3kHz for all units
Voltage Boost
0-25% (Fixed or Auto Boost)
Flux Control
1. V/F control with linear or fan law profile
2. Sensorless vector with automatic flux control and slip
compensation
Slip Compensation
Compensates for motor slip for varying loads
Skip Frequencies
4 skip frequencies with adjustable skip band width
Preset Speeds
8 presets with programmable ramp rates
Stopping Modes
Ramp, ramp with hold, coast, dc injection, fast stop
Ramps
Symmetric or asymmetric ramp up and down rates
Raise/Lower
Programmable MOP function
Jog
Programmable jog speed
Logic Functions
10 programmable 3 input logic function blocks
performing NOT, AND, NAND, OR, NOR and XOR
functions
Value Functions
10 programmable 3 input value function blocks
performing IF, ABS, SWITCH, RATIO, ADD, SUB, RATIO,
TRACK/HOLD, and BINARY DECODE functions
Diagnostics
Full diagnostic and monitoring facilities
Protection
Trip Conditions
Output short line to line, and line to earth
Overcurrent > 220%
I x t overload 50-105% (adjustable)
Heatsink overtemperature
Motor Thermistor overtemperature
Overvoltage and undervoltage
Current Limits
Adjustable 50%-150%
180% shock load limit
Voltage/ Frequency
Profile
Constant torque
Fan Law
Inputs/
Outputs
Analog Inputs
4 user-configurable:
Speed setpoint/trim ±10V, 0-10V, 2-10V, 0-5V, 1-5V
Speed setpoint 4-20, 20-4, 0-20 or 20-0mA
Current loop 4-20, 20-4, 0-20 or 20-0mA
Torque limit 0-10V
Analog Outputs
2 user-configurable:
Speed 0-10V and 0-20mA
Load ±10V
Digital Inputs
8 x 24V dc inputs (user-configurable)
Digital Outputs
3 relay contacts (volt-free)
Table 2-1 Control Features
DEFAULT
Summary of Contents for 605C
Page 16: ...1 4 Getting Started 605C Frequency Inverter ...
Page 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Page 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Page 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Page 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Page 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Page 212: ...13 6 Application Notes 605C Frequency Inverter ...
Page 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Page 236: ......