9-6
Sequencing Logic
605C Frequency Inverter
Communications Status
The COMMS STATUS parameter (Tag 272) in the COMMS CONTROL function block
monitors the sequencing of the Inverter. It is a 16-bit word based on standard fieldbus drive
profiles. Some bits are not implemented in the initial release and are set to 0 (see “Supported”
column of the table below).
Bit
Name
Description
Supported
0
Ready To Switch On
√
1
Switched On
Ready for operation (refer control bit 0)
√
2
Operation Enabled
(refer control bit 3)
√
3
Fault
Tripped
√
4
(Not) Voltage Disabled
OFF 2 Command pending
√
5
(Not) Quick Stop
OFF 3 Command pending
√
6
Switch On Disable
Switch On Inhibited
√
7
Warning
8
SP / PV in Range
9
Remote
= 1 if Drive will accept Command Word
√
10
Setpoint Reached
11
Internal Limit Active
12
13
14
15
Ready To Switch On
Same as the SWITCH ON ENABLE output parameter of the SEQUENCING LOGIC function
block.
Switched On
Same as the SWITCHED ON output parameter of the SEQUENCING LOGIC function block.
Operation Enabled
Same as the RUNNING output parameter of the SEQUENCING LOGIC function block.
Fault
Same as the TRIPPED output parameter of the SEQUENCING LOGIC function block.
(Not) Voltage Disabled
If in REMOTE COMMS mode, this is the same as Bit 1 of the COMMS COMMAND
parameter. Otherwise it is the same as the /COAST STOP input parameter of the
SEQUENCING LOGIC function block.
(Not) Quick Stop
If in REMOTE COMMS mode, this is the same as Bit 2 of the COMMS COMMAND
parameter. Otherwise it is the same as the /FAST STOP input parameter of the SEQUENCING
LOGIC function block.
Switch On Disable
Set (=1) only when in START DISABLED state.
Remote
This bit is set (= 1) if the Inverter is in Remote mode
AND
the parameter REMOTE COMMS
SEL of the COMMS CONTROL function block is Set (= 1).
Summary of Contents for 605C
Page 16: ...1 4 Getting Started 605C Frequency Inverter ...
Page 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Page 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Page 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Page 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Page 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Page 212: ...13 6 Application Notes 605C Frequency Inverter ...
Page 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Page 236: ......