Application Macros
15-4
605C Frequency Inverter
Macro 1: Basic Speed Control (default)
This macro provides standard control of the inverter.
Control Wiring I/O
Terminal
Name
Purpose
Comment
1
ANALOG INPUT 1
Setpoint
0V = 0%, 10V = 100%
2
ANALOG INPUT 2
Setpoint Trim
0V = 0%, 10V = 100%
6
ANALOG OUTPUT 1
Ramp Output
Absolute Speed Demand
0V = 0%, 10V = 100%
13
DIGITAL INPUT 1
Run
24V = Run
14
DIGITAL INPUT 2
Trip Reset
0V to 24V transition
to reset trips.
15
DIGITAL INPUT 3
Direction
0V = Forward, 24V = Reverse
16
DIGITAL INPUT 4
External Trip
0V = Trip
(connect to terminal 18)
17
DIGITAL INPUT 5
Jog
24V = Jog
21, 22
DIGITAL OUTPUT 1
Health
0V = Tripped, i.e. not healthy
23, 24
DIGITAL OUTPUT 2
Running
0V = Stopped, 24V = Running
The Operator Menu System for Macro 1
The default Operator menu system is shown below.
SETPOINT (REMOTE)
SPEED DEMAND
DRIVE FREQUENCY
MOTOR CURRENT
LOAD
DC LINK VOLTS
CURRENT LIMITING
ENTER PASSWORD
STARTUP SCREEN
Summary of Contents for 605C
Page 16: ...1 4 Getting Started 605C Frequency Inverter ...
Page 22: ...2 6 An Overview of the Inverter 605C Frequency Inverter ...
Page 50: ...4 14 Operating the Inverter 605C Frequency Inverter ...
Page 66: ...5 16 The Operator Station 605C Frequency Inverter ...
Page 156: ...8 2 Routine Maintenance and Repair 605C Frequency Inverter ...
Page 184: ...10 22 Parameter Specification 605C Frequency Inverter ...
Page 212: ...13 6 Application Notes 605C Frequency Inverter ...
Page 214: ...14 2 Serial Communications 605C Frequency Inverter ...
Page 236: ......