animeo IB+ 

 

4 Zone/8 Zone TouchBuco BACnet 

30.12.2019 

 

hlp40 

 

 

 

 

 

© 2020, SOMFY ACTIVITES SA . ALL RIGHTS RESERVED . 

REF. 5154229A

 – 2020/01/30 

Summary of Contents for animeo IB+ 4 Zone Touch Building Controller

Page 1: ...animeo IB 4 Zone 8 Zone TouchBuco BACnet 30 12 2019 hlp40 2020 SOMFY ACTIVITES SA ALL RIGHTS RESERVED REF 5154229A 2020 01 30 ...

Page 2: ...opy Run Tilt Times 11 1 13 Password 11 1 14 Save 11 2 Home 11 2 1 Dashboard 12 3 Control 12 3 1 Control 12 3 2 Control all 13 3 3 Control all settings 13 4 Sensors 13 4 1 Outside 13 4 2 Inside 14 5 Log 14 5 1 Event 14 5 2 Sensors 14 5 3 Error 14 5 4 Export 14 6 Settings 15 6 1 Security 15 6 1 1 Alarm 15 6 1 2 Rain Snow 16 6 1 3 Frost Ice 16 6 1 4 Wind 17 6 1 5 Lock Timer 18 6 1 6 Error 19 6 2 Comf...

Page 3: ...osition 35 6 5 1 5 Reset 35 6 5 1 6 Email Notification 35 6 5 2 Moco Settings 36 6 5 2 1 Test Zones 36 6 5 2 2 Learn Zones 37 6 5 2 3 Run Tilt Times 38 6 5 2 4 Switch Config 39 6 5 2 5 My Position 40 6 5 2 6 Lock Motor Controllers 40 6 5 3 Basic Settings 40 6 5 3 1 Date Time 40 6 5 3 2 Locals 40 6 5 3 3 Touch 41 6 5 3 4 Heartbeat 41 6 5 3 5 Password 41 6 5 3 6 Network Config hlp29 Network 41 6 5 4...

Page 4: ...u use sun tracking for the sun protection function When using a fixed position and or an angle this is not necessary You can find the longitude and latitude for your location via the Internet for example via Google Maps Step 1 Navigate to http maps google com via your web browser Step 2 Enter your location Step 3 Right click on the icon and select What is here Step 4 Read off the longitude and lat...

Page 5: ...t being activated i e they do not move to the intended position Possible causes Check the fuses on the motor controller only for 4 unit device The thermal protection may have been activated on one drive e g after many long movements Wait 15 minutes and then repeat the test 1 6 Choose Weather Station You can choose from five options here 1 Compact Sensor compact weather station with integrated sens...

Page 6: ...mple Start with sensor 1 which you may install e g on the north side We then recommend installing sensors 2 3 up to 8 working clockwise i e towards north east east etc 1 8 Choose external wind sensors You have selected the Outside Sensor Box as weather station Now specify which outside sensors are con nected If you have selected the wrong sensors you will later receive an error message since the s...

Page 7: ...typically ena ble a wind alarm for the Venetian blind and not for the roller shutters Aside from this you wish to move the Venetian blind to a position with subsequent slat turning in the event of direct sun In the case of a roller shutter there is no slat turning only an up down command 1 11 Learn Zones After you have checked the wiring of the motor controllers and set up the zones correctly you ...

Page 8: ...ich are to be assigned to the zone 1 4 Enter the ID address of the motor controller in the field and then hit Learn Conversely you can also delete individual motor controller assignments by clicking on Unlearn instead of Learn 1 12 End Product Once you have specified how many zones sections are required you now need to determine which end product is installed on a zone by zone basis This selection...

Page 9: ... up and down Folding arm awning With folding arm awnings the awning cloth of two or more arms is moved and ten sioned The awning cloth can therefore fail in the horizontal direction although a slight inclination is generally set to prevent this With the jointed arm approach the awning arms are angled when retracted and out stretched when extended Vertical fixed louvers tilt only This is a blind ba...

Page 10: ...l by several seconds total distance covered by motorized product moving up and down When using end products motorized products with turning e g Venetian blinds If a position and an angle are to be approached the runtime must be entered very accurately as the rotation for the angle only starts once the runtime entered has elapsed If there are motorized products of varying lengths within a given zon...

Page 11: ...e default password However you can change the password here by clicking on Use Settings Password 1 17 Save Project New You can create a new project file here However the number of project files is restricted to just four due to the memory available Delete Select a file and delete it Overwrite You can overwrite an existing project file here Simply highlight the file and select Overwrite Copy from t...

Page 12: ...uco is active Timer scheduled switching commands Block Heat power save function Solar Heating power save function Maintain Heat power save function Cooling power save function Sun Protection convenience function If multiple functions are active at the same time for example wind and timer only the function with the high est priority will be executed 3 Control 3 1 Control Standard You can move the m...

Page 13: ...Here you can select the zones to be controlled via Control All 4 Sensors In this section all sensors which are connected and in use are displayed as icons together with their current measured values The numbering from 1 to 8 indicates the number of the sensor type used Sensor errors are displayed by means of different symbols This can be caused by various factors Unused sensor C Sensor is selected...

Page 14: ...white forward and backward arrows located at the bottom in the yellow area to navigate through the recordings To return to the main menu simply tap the arrow at the top left 5 1 Event All functional modifications are recorded per zone with their respective status This display is useful when troubleshooting For example if the delay times for the sun protection functions are set too short too many t...

Page 15: ...slider to the right Settings ALARM ON Position of the end product motorized product in the event of an alarm signal Lock Only The end products motorized products in a zone stop moving and low priority manual and auto matic commands are locked Up Priority The end products motorized products in a zone move to the upper end limit and low priority man ual and automatic commands are locked Down Priorit...

Page 16: ...ity manual and automatic commands are locked Down Priority The end products shades in a zone move to the lower end limit and low priority manual and automatic commands are locked 6 1 3 Frost Ice This function is used to protect end products shades from frost cold or ice precipitation cold for safety reasons In the event of a frost ice alarm further operator commands local operation via buttons rad...

Page 17: ...riod at least equal to the Delay Time On the wind function is activated The behavior of the end product motorized product can be defined The delay time off starts counting as soon as the wind speed drops below the threshold The function is released as soon as the delay time off has elapsed Wind function for application ZIP screen If the measured wind speed exceeds the low wind threshold for a peri...

Page 18: ...ts of an area to a position at a certain time adjustable where they remain until enabled By that time further operator commands local operation via buttons radio control etc and low priority automatic commands are locked The IB LED on the motor controller lights up red to indicate that commands have been locked Up to 6 switching commands can be set per week day Monday to Sunday Each switching comm...

Page 19: ...times although not before a certain time in the morning and not after a certain time in the evening Example Let us re examine the above example If the lock time used summer time is set to dawn at 7 00 am the switching command will not be executed until 7 00 am rather than at 5 39 am If the evening lock time used is set to 8 00 pm the switching command is already executed at 8 00 pm rather than at ...

Page 20: ...om this time onwards and low priority functions such as the sun protection function can be reactivated The switching time can either be a fixed time of the day or be calculated automatically based on the dawn and dusk times please see below for an explanation on this You can define and enable a position or in the case of Venetian blinds also the angle so that the motorized products move to the set...

Page 21: ...here are two ways to execute the function One defined position or multiple positions that are calculated on basis of the current position of the sun Sun tracking provides optimum sun protection in natural light conditions Sun protection with a defined position is activated when the outside brightness remains above the Threshold On for longer than the Delay Time On value The end products motorized ...

Page 22: ... width overlap The slats should ideally be aligned horizontally for measuring A typical value is 0 9 Screen Length Only used for sun position tracking with textile sun protection or with roller shutters not for Venetian blinds The height corresponds to the window height Sun Depth Only used for sun position tracking with textile sun protection or with roller shutters not for Venetian blinds How low...

Page 23: ... is not active below this value b To The sun function is not active above this value 2 Azimuth horizontal angle At the set angle from a to b the sun function is active a From The sun function is not active below this value b To The sun function is not active above this value This function is only executed when no other function with higher priority has been activated ...

Page 24: ...ng offers the advantage that a person using the room for a certain time retains control over the automatic commands In Comfort mode all energy functions are deactivated otherwise the function is identical to the Manual Priority operating mode The ENERGY TIMER can be used to enable the various modes via timer The function is enabled when you move the slider to the right You can set up to six switch...

Page 25: ... the switching command is already executed at 8 00 pm rather than at 9 17 pm During winter when the sunrise may not occur until around 7 15 am the lock time used of 7 00 am is disre garded as the sunrise occurs after the lock time used COPY Once you have set up a specific day for example Monday you can then apply this setting to other days of the week To do so simply select the day you wish to cop...

Page 26: ...e standard position The standard position needs to be defined once s chapter 6 5 1 System Settings Position The motorized products moved to the set position In the case of Venetian blinds the defined angle is set My Position The motorized products move to the intermediate position programmed in the motor controller 6 3 3 Solar Heating When the inside temperature is too low solar radiation can be u...

Page 27: ...osition The standard position needs to be defined once s chapter 6 5 1 System Settings Position The motorized products move to a set position In the case of Venetian blinds the defined angle is set My Position The motorized products move to the intermediate position programmed in the motor controller 6 3 4 Maintain Heat This function allows heat to be kept in the building by using sun protection I...

Page 28: ...Maintain Heat Off Setting the position of the motorized product after enabling the function No Action The end products motorized products remain stationary in position Standard The end products motorized products move to the standard position The standard position needs to be defined once s chapter 6 5 1 System Settings Position The end products motorized products move to a set position In the cas...

Page 29: ...tting the position in 100 open Cooling Off Setting the position of the motorized product after enabling the function No Action The end products motorized products remain stationary in position Standard The end products motorized products move to the standard position The standard position needs to be defined once s chapter 6 5 1 System Settings Position The end products motorized products move to ...

Page 30: ... as alter the designations of the individual sensors H Only set up those things that have been connected Tap on the icons to make the settings 6 4 1 Outside Sensors You have five options No Sensor used You have not connected a sensor box Compact Sensor or Outside Sensor Box Compact Sensor A compact weather station with integrated sensors e g for wind 3 x sun outside temperature and rain Outside Se...

Page 31: ...or Box Sensor inputs 1 4 on the device can be used for key switches When activated the top priority is active alarm Sensor inputs 5 8 on the device can be used as area sensors Setting 1 Select the Inside Sensor Box 2 Select the individual Inside Temperature Sensors Select the sensors that are connected The systems will report an error in the case of incorrect selections as it does not receive comp...

Page 32: ...he icon or the arrow below it to make settings for the individual system parameters 6 5 1 1 Location Enter your geographical location H This entry is necessary if you wish to use the defined dusk time for switching times with timer functions with or without disabling function When using a fixed switching time this is not necessary This entry is also required if you use sun tracking for the sun pro...

Page 33: ...n In the case of a roller shutter there is no slat turning only an up down command 6 5 1 3 End Products Once you have specified how many zones are required you now need to determine which end product is installed on a zone by zone basis This selection must be made very accurately as it is critical for smooth functioning of the system For exam ple if you define a Venetian blind as a roller shutter ...

Page 34: ... it reaches around half way when it is then moved into a 45 angle relative to the façade by extending a boom Only moves up and down Folding arm awning With folding arm awnings the awning cloth of two or more arms is moved and ten sioned The awning cloth can therefore fail in the horizontal direction although a slight inclination is generally set to prevent this With the jointed arm approach the aw...

Page 35: ...mit settings menu using the grey arrows Angle end limits Angle end limit default setting on Venetian blinds is 0 or 90 for slats that are fully open or 90 for slats that are fully closed For other motorized products the angle end limits must be adjusted accordingly You can access the motor output inversion menu using the grey arrows Motor output inverted In this menu all output commands for a zone...

Page 36: ...ultimately moved to the limit switch position of their drive Note 1 Down Command means that the end products motorized products roller shutters Venetian blinds etc are being lowered or that a window is being opened 2 Up Command means that the end products motorized products roller shutters Venetian blinds etc are being raised or that a window is being closed 3 Up Command means that the end product...

Page 37: ...en with the new programming process The Learn not assigned Motor Controllers option Motor controllers that have already been programmed are excluded from assignment here This prevents existing assignments from being overwritten by mistake You can tell when a motor controller is in programming mode as the unit s LEDs run a circulating pattern With the Smoove UNO IB the LED flashes in various colors...

Page 38: ...enter the longest time first You can make precision adjustments for the shorter motorized products in this zone later under Settings Angle The angle is the time required by a Venetian blind to turn the slats from fully closed to fully open This time is typically in the range from 0 8 to 2 seconds H Positioning accuracy better than 5 is generally not achieved This is due to the mechanical systems e...

Page 39: ...D address You can find this on the barcode sticker on the motor controller example ID 8390363 With the Smoove UNO IB the address is printed on the rear of the front panel If desired determine the motor controller outputs drives that are to receive this data Then hit Send 6 5 2 4 Switch Config With animeo IB 2 4 6 unit Motor Controllers each Motor Controller output has a sensor input for local oper...

Page 40: ...verwritten by the setting on the TouchBuco Setting Enter the position in and the angle in Hit Send to transfer the data entered 6 5 2 6 Lock Motor Controllers You can use this function to lock and unlock all Motor Controllers within a zone together or individually via ID number This means that no settings can be changed such as runtimes when locked 6 5 3 Basic Settings You can make basic settings ...

Page 41: ...e to a cable break the end products motorized products move to their safety position Repeat this for all zones as necessary 6 5 3 5 Password Assigning a password prevents unauthorized persons from changing parameters during operation somfy is set as the default password However you can change the password here Setting Use Control Password provides you with access to the operating controls The cont...

Page 42: ...ew project file here Delete Select a file and delete it Load You can load a previously saved project file here Overwrite Here you can update an existing project file after changes to the project Copy from to USB You can copy project files from and to a USB stick here 6 5 5 Update Motor Controllers This function allows the current motor controller settings to be transferred to the individual zones ...

Page 43: ...BV100 Shows status of external alarm input LOCK_BV BINARY VALUE BV101 Shows that local control is locked Control via TouchBuco is still possible ERROR_BV BINARY VALUE BV102 Shows critical defect of wind sensor wind direction sensor and Outside Sensor Box WIND_BV BINARY VALUE BV103 Shows that wind function is active due to exceeded wind threshold and on delay time SNOW_FROST_ICE_RAIN_BV BINARY VALU...

Page 44: ...de fined time or period BLOCK_HEAT_BV BINARY VALUE BV208 Shows that the blinds are closed to avoid the room from overheating SOLAR_HEATING_BV BINARY VALUE BV209 Shows that the blinds are opened to take advantage of the sun MAINTAIN_HEAT_BV BINARY VALUE BV210 Shows that the blinds are closed to pre vent the room from cooling out COOLING_BV BINARY VALUE BV211 Shows that the windows are opened to tak...

Page 45: ...00 98 Percent Write a value between 0 and 100 to move the blinds to the desired position BLIND_ANGLE_ ANALOG VALUE AV301 90 Degree angular Write a value between 0 and 90 or 90 and 90 to move the blinds to the desired angle ALARM_BV BINARY VALUE BV400 Shows status of external alarm input LOCK_BV BINARY VALUE BV401 Shows that local control is locked Control via TouchBuco is still possible ERROR_BV B...

Page 46: ...V507 Shows that an order is sent for a pre de fined time or period BLOCK_HEAT_BV BINARY VALUE BV508 Shows that the blinds are closed to avoid the room from overheating SOLAR_HEATING_BV BINARY VALUE BV509 Shows that the blinds are opened to take advantage of the sun MAINTAIN_HEAT_BV BINARY VALUE BV510 Shows that the blinds are closed to pre vent the room from cooling out COOLING_BV BINARY VALUE BV5...

Page 47: ...00 98 Percent Write a value between 0 and 100 to move the blinds to the desired position BLIND_ANGLE_ ANALOG VALUE AV601 90 Degree angular Write a value between 0 and 90 or 90 and 90 to move the blinds to the desired angle ALARM_BV BINARY VALUE BV600 Shows status of external alarm input LOCK_BV BINARY VALUE BV701 Shows that local control is locked Control via TouchBuco is still possible ERROR_BV B...

Page 48: ...erature LOCK_TIMER_BV BINARY VALUE BV805 Shows that local control is locked for a pre defined period MANUAL_BV BINARY VALUE BV806 Shows that a manual command is exe cuted TIMER_BV BINARY VALUE BV807 Shows that an order is sent for a pre de fined time or period BLOCK_HEAT_BV BINARY VALUE BV808 Shows that the blinds are closed to avoid the room from overheating SOLAR_HEATING_BV BINARY VALUE BV809 Sh...

Page 49: ......