HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 29 of 77
No
Type
Description
18
Gen Phase
Sequence Wrong
When the controller detects a phase rotation error, it will
initiate a warning alarm.
19
Switch Fail Warn
When the controller detects that the breaker close or open
failure occurs, and the action select “Warn”, it will initiate a
warning alarm.
20
Temperature Sensor
Open Circuit
When the controller detects that the temperature sensor is
open circuit and the action select “Warn”, it will initiate a
warning alarm.
21
High Temperature
When the controller detects that engine temperature has
exceeded the pre-set value, it will initiate a warning alarm.
22
Low Temperature
When the controller detects that engine temperature has
fallen below the pre-set value, it will initiate a warning alarm.
23
Oil Pressure Open
Circuit
When the controller detects that the oil pressure sensor is
open circuit and the action select “Warn”, it will initiate a
warning alarm.
24
Low Oil Pressure
When the controller detects that the oil pressure has fallen
below the pre-set value, it will initiate a warning alarm.
25
Level Sensor Open
Circuit
When the controller detects that the level sensor is open
circuit and the action select “Warn”, it will initiate a warning
alarm.
26
Low Fuel Level
When the controller detects that the fuel level has fallen
below the pre-set value, it will initiate a warning alarm.
27
Flexible Sensor 1
Open Circuit
When the controller detects that the flexible sensor 1 is open
circuit and the action select “Warn”, it will initiate a warning
alarm.
28
Flexible Sensor 1
High
When the controller detects that the sensor 1 value has
exceeded the pre-set value, it will initiate a warning alarm.
29
Flexible Sensor 1
Low
When the controller detects that the sensor 1 value has fallen
below the pre-set value, it will initiate a warning alarm.
30
Flexible Sensor 2
Open Circuit
When the controller detects that the flexible sensor 2 is open
circuit and the action select “Warn”, it will initiate a warning
alarm.
31
Flexible Sensor 2
High
When the controller detects that the sensor 2 value has
exceeded the pre-set value, it will initiate a warning alarm.
32
Flexible Sensor 2
Low
When the controller detects that the sensor 2 value has fallen
below the pre-set value, it will initiate a warning alarm.
33
Digital Input
When digit input port is set as warning and the alarm is
active, it will initiate a warning alarm.
34
GSM Com Fail
When select GSM enable but the controller couldn’t detect
GSM model, controller sends corresponding warning signal.
35
Earth Fault
If earth fault detection is enabled, when the controller detects
that the earth fault current has exceeded the pre-set value
and the action select “Warn”, it will initiate a warning alarm.