HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 56 of 77
start automatically; when input inactive, genset
will stop automatically
31
Reserved
32
Reserved
33
Simulate Stop Key
An external button can be connected and pressed
as simulate panel.
34
Simulate Manual Key
35
Reserved
36
Simulate Auto Key
An external button can be connected and pressed
as simulate panel.
37
Simulate Start Key
38
Simulate G-Load Key
This is simulate
G-close key when
HGM9310MPU(CAN) controller is applied.
39
Simulate M-Load Key
This is simulate
M-open key when
HGM9310MPU(CAN) controller is applied.
40
Low Coolant Level
Connect with water level sensor digital input port.
41
Detonation Shut
Connect with detection module warn input port.
42
Reserved
43
Reserved
44
Reserved
45
Aux Mains OK
In
Auto
mode, mains are normal when input is
active.
46
Aux Mains Fail
In
Auto
mode, mains are abnormal when input is
active.
47
Alternative Config1
Alternative configuration is active when the input
is active. Users can set different parameters to
make it easy to select current configuration via
input port.
48
Alternative Config2
49
Alternative Config3
50
Gas Leak Shut
Connect with detection module warn input port.