HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 73 of 77
15.13 MTU ADEC(SAM MODULE)
It is suitable for MTU engine with ADEC (ECU7) and SAM module.
Terminals of controller
ADEC (X1port)
Remark
Fuel relay output
X1 43
X1 Terminal 28 Connected to
negative of battery
Start relay output
X1 37
X1 Terminal 22 Connected to
negative of battery
Terminals of controller
SAM (X23 port)
Remark
CAN GND
X23 3
CAN communication shielding
line(connect with controller’s this
terminal only)
CAN(H)
X23 2
I
mpedance 120Ω connecting line
is recommended.
CAN(L)
X23 1
Impedance 120Ω connecting line
is recommended.
Engine type: Common J1939
15.14 PERKINS
It is suitable for ADEM3/ ADEM4 engine control module. Engine type is 2306, 2506, 1106,
and 2806.
Terminals of controller
Connector
Remark
Fuel relay output
1,10,15,33,34
Start relay output
-
Connect to starter coil directly
CAN GND
-
CAN communication shielding
line(connect with controller’s
terminal only)
CAN(H)
31
Impedance 120Ω connecting line
is recommended.
CAN(L)
32
Impedance 120Ω connecting line
is recommended.
Engine type: Perkins