HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 36 of 77
No.
Function
Cable
Size
Remarks
43
Mains C-phase
voltage input
1.0mm
2
Connected to C-phase of mains (2A fuse is
recommended).
(HGM9310MPU, HGM9310CAN without).
44
Mains N-wire input
1.0mm
2
Connected to N-wire of mains.
(HGM9310MPU, HGM9310CAN without).
45
Genset A-phase
voltage input
1.0mm
2
Connected to A-phase of gen-set (2A fuse is
recommended).
46
Genset B-phase
voltage input
1.0mm
2
Connected to B-phase of gen-set (2A fuse is
recommended).
47
Genset C-phase
voltage input
1.0mm
2
Connected to C-phase of gen-set (2A fuse is
recommended).
48
Genset N-wire
input
1.0mm
2
Connected to N-wire of gen-set.
49
CT A-phase input
1.5mm
2
Outside connected to secondary coil of current
transformer(rated 5A).
50
CT B-phase input
1.5mm
2
Outside connected to secondary coil of current
transformer(rated 5A).
51
CT C-phase input
1.5mm
2
Outside connected to secondary coil of current
transformer(rated 5A).
52
CT COM
1.5mm
2
See following installation instruction.
53
Earth Current
1.5mm
2
Outside connected to secondary coil of current
transformer(rated 5A).
54
1.5mm
2
55
Aux. Input 8
1.0mm
2
Ground connected is active
(B-).
Details see form
3.
56
Aux. sensor 1
1.0mm
2
Connected to temperature, oil
pressure or level sensors.
Details see form
4.
57
Aux. sensor 2
1.0mm
2
58
Oil pressure sensor
1.0mm
2
Connected to oil pressure
sensor.
59
Temperature sensor
1.0mm
2
Connected to temperature
sensor.
60
Fuel level sensor
1.0mm
2
Connected to fuel level
sensor.
61
Sensor COM
/
Public terminal of sensor, (B-) has already
connected.
62
RS232
0.5mm
2
Connected to GSM module.
63
RS232 RX
0.5mm
2
64
RS232 TX
0.5mm
2
NOTE:
USB ports in controller rear panel are programmable parameter ports, user can
directly configure controller via PC.
NOTE:
Please refer to the Module Comparison in this manual for more details.