HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 39 of 77
No.
Items
Parameters
Defaults
Description
4
Speed on Load (0~100)%
90%
Setting value is percentage of rated
speed. Controller detects when it is
ready to load. It won’t switch on when
speed is under loading speed.
5
Loss of Speed
Signal
(0~3600)s
5
Time from detecting speed is 0 to
confirm the action.
6
Loss of Speed
Action
(0~1)
0
0:Warn; 1:Shutdown
7
Over Speed
Shutdown
(0~200)%
114%
Setting value is percentage of rated
speed and delay value (Over Speed
default: 2s; Under Speed default: 3s)
can be set.
8
Under Speed
Shutdown
(0~200)%
80%
9
Over Speed
Warn
(0~200)%
110%
Setting value is percentage of rated
speed. Delay value (default: 5s) and
return value (Over Speed default:
108; Under Speed default: 90) also
can be set.
10
Under Speed
Warn
(0~200)%
86%
11
Battery Rated
Voltage
(0~60.0)V
24.0
Standard for detecting over/under
voltage of battery.
12
Battery Over
Volts
(0~200)%
120%
Setting value is percentage of rated
voltage of battery. Delay value
(default: 60s) & return value (Over
Volts default: 115; Under Volts
default: 90) can be set.
13
Battery Under
Volts
(0~200)%
85%
14
Charge Alt Fail (0~60.0)V
8.0
In normal running, when charger
D+(WL) voltage under this value,
charge failure alarms.
15
Start Attempts
(1~10) times
3
Max. Crank times of crank attempts.
When reach this number, controller
will send start failure signal.
16
Crank
Disconnect
(0~6)
2
See form 5
There are 3 conditions of
disconnecting starter with engine.
Each condition can be used alone
and simultaneously to separating the
start motor and genset as soon as
possible.
17
Disconnect
Generator Freq
(0~200)%
24%
When generator frequency higher
than the set value, starter will be
disconnected. See the installation
instruction.
18
Disconnect
Engine Speed
(0~200)%
24%
When generator speed higher than
the set value, starter will be