HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 31 of 77
No Type
Description
17
High Temperature
When the controller detects that engine temperature has
exceeded the pre-set value, it will initiate a shutdown alarm.
18
Oil Pressure Open
Circuit
When the controller detects that the oil pressure sensor is
open circuit and the action select “Shutdown”, it will initiate a
shutdown alarm.
19
Low Oil Pressure
When the controller detects that the oil pressure has fallen
below the pre-set value, it will initiate a shutdown alarm.
20
Level Sensor Open
Circuit
When the controller detects that the level sensor is open
circuit and the action select “Shutdown”, it will initiate a
shutdown alarm.
21
Flexible Sensor 1
Open Circuit
When the controller detects that the flexible sensor 1 is open
circuit and the action select “Shutdown”, it will initiate a
shutdown alarm.
22
Flexible Sensor 1
High
When the controller detects that the sensor 1 value has
exceeded the pre-set value, it will initiate a shutdown alarm.
23
Flexible Sensor 1
Low
When the controller detects that the sensor 1 value has fallen
below the pre-set value, it will initiate a shutdown alarm.
24
Flexible Sensor 2
Open Circuit
When the controller detects that the flexible sensor 2 is open
circuit and the action select “Shutdown”, it will initiate a
shutdown alarm.
25
Flexible Sensor 2
High
When the controller detects that the sensor 2 value has
exceeded the pre-set value, it will initiate a shutdown alarm.
26
Flexible Sensor 2
Low
When the controller detects that the sensor 2 value has fallen
below the pre-set value, it will initiate a shutdown alarm.
27
Digital Input
When digit input port is set as shutdown and the alarm is
active, it will initiate a shutdown alarm.
28
Earth Fault
If earth fault detection is enabled, when the controller detects
that the earth fault current has exceeded the pre-set value
and the action select “Shutdown”, it will initiate a shutdown
alarm.
29 Low Coolant Level
Controller initiate shutdown alarm after digital input port been
configured aslow coolant level shutdown ( is active).
30 Detonation Shutdown
Controller initiate shutdown alarm after digital input port been
configured as detonation shutdown ( is active).
31 Gas Leak Shutdown
Controller initiate shutdown alarm after digital input port been
configured as gas leak shutdown ( is active).