HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 54 of 77
when inactive);
When input port 1 active or input port 2 active, if input port 3 is active, Defined combination
output is outputting; If input port 3 inactive, Defined combination output is not outputting;
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not,
Defined combination output is not outputting.
8.3 DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS (ALL
ACTIVE WHEN CONNECT TO GRAND (B-))
Form 3
No.
Type
Description
0
Users Configured
Including following functions,
Indication: indicate only, not warning or shutdown.
Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Trip and stop: alarm, generator unloads and
shutdown after hi-speed cooling
Trip: alarm, generator unloads but not shutdown.
Never: input inactive.
Always: input is active all the time.
From crank: detecting as soon as start.
From safety on: detecting after safety on run
delay.
1
Reserved
2
Alarm Mute
Can prohibit “Audible Alarm” output when input is
active.
3
Reset Alarm
Can reset shutdown alarm and trip alarm when
input is active.
4
60Hz Active
Use for CANBUS engine and it is 60Hz when
input is active.
5
Lamp Test
All LED indicators are illuminating when input is
active.
6
Panel Lock
All buttons in panel is inactive except
and there is in the left of
first row in LCD when input is active.
7
Reserved
8
Idle Control Mode
Under voltage/frequency/speed protection is
inactive.
9
Inhibit Auto Stop
In
Auto
mode, during generator normal running,
when input is active, inhibit generator shutdown
automatically.
10
Inhibit Auto Start
In
Auto
mode, inhibit generator start automatically