HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 35 of 77
No.
Function
Cable
Size
Remarks
10
Aux. Input 1
1.0mm
2
Ground connected is active
(B-).
Details see form
3
11
Aux. Input 2
1.0mm
2
Ground connected is active
(B-).
12
Aux. Input 3
1.0mm
2
Ground connected is active
(B-).
13
Aux. Input 4
1.0mm
2
Ground connected is active
(B-).
14
Aux. Input 5
1.0mm
2
Ground connected is active
(B-).
15
Aux. Input 6
1.0mm
2
Ground connected is active
(B-).
16
Magnetic Pickup
0.5mm
2
Connected with Speed sensor, shielding line is
recommended. (B-) has already connected with
speed sensor 2.
17
Magnetic Pickup 2
18
Magnetic Pickup 1
19
Aux. Input 7
1.0mm
2
Ground connected is active
(B-).
Details see form
3.
20
Aux. Output 4
1.5mm
2
Normally close output, rated
7A.
Details see form
2.
21
Public points of relay.
22
Normally open output, rated
7A.
23
ECU CAN
/
Impedance-120
Ω shielding wire is recommended,
its single-end earthed.
(HGM9310MPU, HGM9310CAN without).
24
ECU CAN H
0.5mm
2
25
ECU CAN L
0.5mm
2
26
RESERVE
/
Empty terminal
33
RS485
/
Impedance-
120Ω shielding wire is recommended,
its single-end earthed.
34
RS485+
0.5mm
2
35
RS485-
0.5mm
2
36
Aux. Output 5
2.5mm
2
Normally close output, rated
7A.
Details see form
2.
37
2.5mm
2
Normally open output, rated
7A.
38
2.5mm
2
Public points of relay
39
Aux. Output 6
2.5mm
2
Normally open output, rated
7A.
40
2.5mm
2
Public points of relay
41
Mains A-phase
voltage input
1.0mm
2
Connected to A-phase of mains (2A fuse is
recommended).
(HGM9310MPU, HGM9310CAN without).
42
Mains B-phase
voltage input
1.0mm
2
Connected to B-phase of mains (2A fuse is
recommended).
(HGM9310MPU, HGM9310CAN without).