29
Close Generator
Control generator to take load.
30
Open Breaker
Control generator to off load.
31
Close Mains
Control mains to take load.
32
Reserved
33
Start Relay
34
Fuel Relay
Action when genset is cranking and disconnect when
stopped completely.
35
Idle Control
Used for engine which has idles. Close before starting
and open in warming up delay; Close during stopping
idle mode and open when stop is completed.
36
Raise Speed
Action in warming up delay.
37
Drop Speed
Action between the period from “stop idle” to “failed to
stop”.
38
ETS Control
Used for engines with ETS electromagnet. Close when
stop idle is over and open when pre-set “ETS delay” is
over.
39
Pulse Drop speed
Active 0.1s when controller enters into stop idle, used
for control part of ECU dropping to idle speed.
40
ECU Stop
Used for ECU engine and control its stop.
41
ECU Power
Used for ECU engine and control its power.
42
Pulse Raise Speed
Active 0.1s when controller enters into warming up
delay; used for control part of ECU raising to normal
speed.
43
Crank Success
Close when detects a successful start signal.
44
Generator OK
Action when generator is normal.
45
Generator Available
Action in period of generator is normal running to
hi-speed cooling.
46
Mains OK
Action when mains is normal.
47
Reserved
48
Common Alarm
Action when genset common warning, common
shutdown, common trips alarm.
49
Common Trip and Stop Action when common trip and stop alarm.
50
Common Shutdown
Action when common shutdown alarm.
51
Common Trip Alarm
Action when common trips alarm.
52
Common Warning Alarm Action in common warning alarm.
53
Reserved
54
Battery High Volts
Action when battery’s over voltage warning alarm.
55
Battery Low Volts
Action when battery’s low voltage warning alarm.
56
Charge Alt Fail
Action when charge failure warning alarms.
57
Reserved
58
Reserved
59
Reserved
60
ECU Warn
Indicate ECU sends a warning signal.
61
ECU Shutdown
Indicate ECU sends a shutdown signal.
62
ECU Com Fail
Indicate controller not communicates with ECU.