HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 24 of 77
5.5 MANUAL START/STOP OPERATION
1. MANUAL START: Manual mode is selected by pressing the
button; a LED besides
the button will illuminate to confirm the operation; then press
button to start the
gen-set; can detect crank disconnect condition and generator accelerates to high-speed
running automatically. With high temperature, low oil pressure, over speed and abnormal
voltage during generator running, controller can protect genset to stop quickly. Press
(HGM9320MPU, HGM9320CAN) or
/
(HGM9310MPU, HGM9310CAN) can
control the switch to close or open. (please refer to No.4~9 of Automatic Start Sequence
for detail procedures; it is noted that the switch close/open ways are different)
2. MANUAL STOP: Press
can stop the running generators. (please refer to No.3~8
of Automatic Stop Sequence for detail procedures).
NOTE: In “manual mode”, the procedures of ATS please refer to
Switch Control
Procedure
of generator in this manual.