HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 40 of 77
No.
Items
Parameters
Defaults
Description
disconnected. See the installation
instruction.
19
Disconnect Oil
Pressure
(0~1000)kPa
200
When generator oil pressure higher
than the set value, starter will be
disconnected. See the installation
instruction.
Generator Setting
1
AC System
(0~3)
0
0: 3P4W; 1: 3P3W;
2: 2P3W; 3: 1P2W.
2
Poles
(2~64)
4
Numbers of generator pole, used for
calculating starter rotate speed when
without speed sensor.
3
Rated Voltage
(30~30000)V
230
To offer standards for detecting of
generator’ over/under voltage and
loading voltage. (It is primary voltage
when using voltage transformer).
4
Loading
Voltage
(0~200)%
85%
Setting value is percentage of
generator rated voltage. Detect when
controller ready to loading. If
generator voltage under load voltage,
won’t enter into normally running.
5
Rated
Frequency
(10.0~600.0)Hz 50.0
To offer standards for detecting of
over/under/load frequency.
6
Loading
Frequency
(0~200)%
85%
Setting value is percentage of
generator rated frequency. Detect
when controller ready to loading.
When generator frequency under
load frequency, it won’t enter into
normal running.
7
Volt.
Trans.(PT)
(0~1)
0
0: Disable; 1:Enable
8
Over Volt.
Shutdown
(0~200)%
120%
Setting value is percentage of
generator rated volt. Delay value
(default: 3s) can be set.
9
Under
Volt.
Shutdown
(0~200)%
80%
10
Over Freq.
Shutdown
(0~200)%
114%
Setting value is percentage of
generator rated freq. Delay value
(Over Freq. default: 2s; Under Freq.
default: 3s) can be set.
11
Under Freq.
Shutdown
(0~200)%
80%
12
Over Volt.
Warn
(0~200)%
110%
Setting value is percentage of
generator rated volt. Delay value
(default: 5s) and return value (Over
Volt. default: 108; Under Volt. default:
13
Under
Volt.
Warn
(0~200)%
84%