HGM93XX MPU(CAN) SERIES GENSET CONTROLLER
HGM93XX MPU(CAN) Series Genset Controller Version: 1.1 2016-11-03 Page 41 of 77
No.
Items
Parameters
Defaults
Description
86) can be set.
14
Over Freq.
Warn
(0~200)%
110%
Setting value is percentage of
generator rated frequency. Delay
value (default: 5s) and return value
(Over Freq. default: 108; Under Freq.
default: 86) can be set.
15
Under Freq.
Warn
(0~200)%
84%
16
Loss of Phase (0~1)
1
0: Disable 1: Enable
17
Phase
Sequence
Wrong
(0~1)
1
Load Setting
1
Current Trans.
(5~6000)/5
500/5
The ratio of external CT
2
Full Current
Rating
(5~6000)A
500
Generator’s rated current, standard
of load current.
3
Full kW rating
(0~6000)kW
276
Generator’s rated power, standard of
load power.
4
Over Current
(0~200)%
120%
Setting value is percentage of
generator rated full current. Delay
value can be set as definite time and
inverse definite minimum time.
5
Over Power
(0~1)
0
0: Disable 1: Enable
6
Reverse Power (0~1)
0
0: Disable 1: Enable
7
Earth Fault
(0~1)
0
0: Disable 1: Enable
Switch Setting
1
Transfer Time
(0~7200)s
5
Interval time from mains switch off to
generator switch on; or from
generator switch off to mains switch
on.
2
Close Time
(0~20.0)s
5.0
Pulse width of mains/generator
switch on. When it is 0, means output
constantly.
3
Open Time
(0~20.0)s
3.0
Pulse width of mains/generator
switch off.
4
Check Time
(0~20.0)s
5.0
Time of detecting switch auxiliary
contacts after transferred.
5
Warn Enable
(0~1)
0
0: Disable 1: Enable
6
Check Enable
(0~1)
0
0: Disable 1: Enable
7
Enable
immediate
mains Dropout
(0~1)
1
0: Disable 1: Enable
Module Setting
1
Power
on
Mode
(0~2)
0
0:
Stop mode
1:
Manual mode
2:
Auto mode