86
Operating Instructions ACU
09/08
If an error message is displayed, the rated values must be checked and corrected.
The guided commissioning procedure is repeated until the rated values have been
entered correctly. Aborting the guided commissioning procedure by pressing ESC
key should only be done by expert users because it may be possible that rated val-
ues have not been entered or determined correctly.
Error Messages
Code
Measures / Remedy
SF000 No error message exists.
SF001 The value entered for parameter
Rated current
371 is too low. Correct the
value.
SF002
The value for parameter
Rated current
371 is too high, referred to para-
meters
Rated power
376 and
Rated voltage
370. Correct the values.
SF003 The value entered for parameter
Rated cos phi
374 is wrong (greater than
1 or smaller than 0.3). Correct the value.
SF004
The calculated slip frequency is negative. Correct the values entered for
parameters
Rated speed
372 and
Rated frequency
375.
SF005
The calculated slip frequency is too high.
Correct the values entered for parameters
Rated speed
372 and
Rated
frequency
375.
SF006
The calculated total output of the drive is lower than the rated power.
Correct the value entered for parameter
Rated power
376.
SF007
The set configuration is not supported by the guided commissioning. For
parameter
Configuration
30, select one of the configurations described in
these operating instructions.
Operating Instructions ACU
09/08
86