Operating Instructions ACU
221
17.6
V-belt Monitoring
Continuous monitoring of the load behavior and thus of the connection between the
3-phase machine and the load is the task of the V-belt monitoring system. The para-
meter
Operation mode
581 defines the function behavior if the
Active current
214
(sensorless control) or the torque-forming current component
Isq
216 (field-oriented
control method) is below the set
Trigger limit Iactive
582 for longer than the para-
meterized
Delay time
583.
Operation mode
581
Function
0 - Off
The function is deactivated.
1
- Warning
If the active current drops below the threshold value,
the warning "A8000" is displayed.
2
- Error
The unloaded drive is switched off and fault message
"F0402" is displayed.
The error and warning messages can be read out by means of the digital outputs
(signal 22 - “Warning V-Belt”) or reported to an overriding control system. The
Trig-
ger limit Iactive
582 is to be parameterized as a percentage of the
Rated current
371
for the application and the possible operating points.
Parameter
Settings
No.
Description
Min.
Max.
Fact. sett.
582 Trigger limit Iactive
0.1 %
100.0 %
10.0 %
583 Delay time
0.1 s
600.0 s
10.0 s
17.7
Functions of Field-Orientated Control
The field-orientated control systems are based on a cascade control and the calcula-
tion of a complex machine model. The various control functions can be supplemented
by special functions specific to the application.
17.7.1 Motor Chopper
The field-orientated control systems contain the function for adapted implementation
of the generator energy into heat in the connected three-phase machine. This en-
ables the realization of dynamic speed changes at minimum system costs. The torque
and speed behavior of the drive system is not influenced by the parameterized brak-
ing behavior. The parameter
Trigger threshold
507
of the DC link voltage defines the
switch-on threshold of the motor chopper function.
Parameter
Settings
No.
Description
ACU
Min.
Max.
Fact. sett..
506
Trigger threshold
201 225
1000.0 V
385
401 425
770
Operating Instructions ACU
221
09/08